Delivering 45A of reliable power, this single-pole Eaton MCCB is designed for industrial environments. The Series C F-Frame breaker provides essential thermal-magnetic trip functions. The bolt-on design ensures a stable connection within compatible Eaton switchboards and distribution panels. It substitutes legacy FDB1045 and FD1045 breakers. Handling 14kA fault currents at 277VAC, this unit features reverse feed capability and an HACR rating for HVAC circuits.
Can the Eaton EHD1045 replace older Westinghouse or Cutler-Hammer breakers with the same catalog number?
Yes. Eaton acquired the Westinghouse and Cutler-Hammer circuit breaker lines. An Eaton EHD1045 is the direct replacement for older Westinghouse and Cutler-Hammer breakers sharing the EHD1045 catalog number.
Which panelboards are compatible with the EHD1045 circuit breaker?
This F-frame breaker is designed for use in Eaton Series C panelboards, including Pow-R-Line models such as PRL1a, PRL2a, PRL3a, and PRL4. It is also compatible with Eaton switchboards and motor control centers.
What does the F-frame designation mean for the EHD1045?
The F-frame designation refers to the physical size and standardized dimensions of the breaker within the Eaton Series C family. All F-frame breakers share the same footprint, which simplifies panelboard design and allows for easier upgrades or replacements without modifying the panel layout.
Are the lug terminals on the EHD1045 rated for both copper and aluminum wire?
Yes, the factory-installed lugs are dual-rated for both copper and aluminum conductors. They accept wire sizes ranging from 14 AWG to 1/0 AWG. Always refer to the breaker nameplate for the correct terminal torque values during installation.
What is the advantage of the bolt-on connection for the EHD1045?
Bolt-on breakers like the EHD1045 are secured directly to the panelboard bus with screws or bolts. This creates a highly reliable, vibration-resistant connection that is preferred in heavy commercial and industrial environments compared to standard plug-on designs.
Can the EHD1045 be used in direct current (DC) control circuits?
Yes. While commonly used for 277VAC applications, this breaker is also UL listed for 125VDC systems with a 10kA interrupting capacity. This dual rating allows it to be used in industrial DC control panels and battery systems.
Does the EHD1045 provide ground fault (GFCI) or arc fault (AFCI) protection?
No. This is a standard thermal-magnetic circuit breaker. It provides long-time and instantaneous (LI) trip functions for overload and short-circuit protection, but it does not include GFCI or AFCI circuitry.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 13 reviews.