| Brand | Eaton / Cutler-Hammer |
|---|---|
| Series | QBGFEP |
| Amperage | 30A |
| Poles | 2 |
| Mounting Style | Bolt-On |
| Voltage | 120/240VAC |
| Phase | 1 |
| AIC Rating | 10kA @ 120/240VAC |
| Terminal Type | Box Lugs |
|---|---|
| For Use With | Eaton Pow-R-Line Panelboards |
| Wire Gauge | 14-4 AWG |
| Max Wire | 4 AWG |
| Min Wire | 14 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LIG |
| Trip Function | Long-Time, Instantaneous, Ground Fault |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Special Classification | GFEP |
|---|---|
| Available Options | Auxiliary Switch, Padlock Attachment |
| Accessories | Load Side Lugs Included, Bell Alarm (Factory Installed) |
| Standards | CSA C22.2 No. 5, UL 1053, UL 489 |
| Approval | CSA, HACR, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Non-Interchangeable Trip |
The W1 suffix indicates that this breaker includes a factory-installed bell alarm. This provides an external signal to alert facility personnel when the breaker trips due to an overcurrent or ground fault condition.
This Ground Fault Equipment Protection (GFEP) breaker has a 30 mA trip sensitivity. It is designed to protect heat trace cables and industrial machinery from sustained line-to-ground faults, unlike Class A GFCI breakers which trip at 5 mA for personnel protection.
This bolt-on Quicklag breaker installs directly into Eaton Cutler-Hammer Pow-R-Line panelboards, such as the PRL1a, PRL2a, PRL1X, and PRL2X series designed for bolt-on branch devices.
No, this is a bolt-on circuit breaker designed specifically for commercial panelboards with bolted bus connections. For plug-on load center applications, a QPGFEP series breaker is required.
This breaker is equipped with a pigtail neutral. The coiled white wire must be routed and terminated at the panelboard neutral assembly to properly power the internal 30 mA ground fault sensing circuitry.
The LIG designation indicates that the breaker provides Long-Time (thermal overload), Instantaneous (magnetic short-circuit), and Ground Fault (30 mA equipment protection) trip functions.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.