ABB / General ElectricSKLB36BB1200
Quantity
New
Quantity
ABB / General ElectricSKLB36BB1200
ABB / General ElectricSKLB36BC1200
ABB / General ElectricSKHA36AT1200
| Brand | ABB / General Electric |
|---|---|
| Part Number | SKHB36BD1200 |
| Series | SKHB |
| Amperage | 1200A |
| Poles | 3 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480VAC, 600VAC |
| Phase | 3 |
| AIC Rating | 65kA @ 240VAC, 50kA @ 480VAC, 25kA @ 600VAC |
| Amperage Range | 600-1200A |
|---|
| Frame Type | SKHB |
|---|---|
| Terminal Type | Lugs |
| For Use With | Spectra Series Switchboards, Spectra Series Power Panelboards, Spectra Series Motor Control Centers |
| Trip Technology | Electronic Trip |
|---|---|
| Trip Function Code | LSIG |
| Trip Function | Long-Time, Short-Time, Instantaneous, Ground Fault |
| Trip Adjustability | Adjustable |
| Available Options | Lugs, Rating Plugs, Shunt Trip, Auxiliary Switch, Undervoltage Release, Bell Alarm |
|---|---|
| Accessories | MicroVersaTrip Plus Trip Unit |
| Standards | CSA C22.2 No. 5, IEC 60947-2, UL 489 |
| Approval | CE, CSA, IEC, UL |
| Temp Rating | 40C |
| Construction Features | True RMS Sensing, Reverse Feed, Current Limiting, Visual Trip Indicator, Interchangeable Trip Unit, HACR Rated |
This breaker is designed for use in General Electric Spectra Series Switchboards, Spectra Series Power Panelboards, and Spectra Series Motor Control Centers.
The continuous current rating is established using a field-installable rating plug. Because it features an electronic trip unit, you must install a compatible SK1200 frame rating plug, such as the SRPK1200A1200, to match your specific load requirements up to 1200 amps.
For cable connections on the SK1200 frame, compatible General Electric lug kits include the TCAL124 and TCAL125, depending on your specific wire size and conductor requirements.
Following ABB's acquisition of GE Industrial Solutions, the Spectra RMS series was replaced by the Tmax XT line. You can upgrade to the ABB XT7SU312EGFF000XXX breaker by utilizing the SRFB3XT7MFPX retrofit kit to fit your existing Spectra equipment.
No, the integrated LSIG electronic trip unit includes built-in ground fault protection. This allows for equipment ground fault monitoring directly from the breaker without the need for an external relay system.
No, this is a heavy-duty bolt-on molded case circuit breaker. It must be bolted directly to the busbars within compatible Spectra Series enclosures and is not designed for DIN rail mounting.
The trip targets are visual indicators on the electronic trip unit that display which specific fault condition (Long-Time, Short-Time, Instantaneous, or Ground-Fault) caused the breaker to trip. This aids electricians in rapid troubleshooting after a fault.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.