ABB / General ElectricSKLC3612L4XX
Quantity
New
Quantity
ABB / General ElectricSKLC3612L4XX
ABB / General ElectricSKLC3612L5XX
ABB / General ElectricSKLC3612L7XX
ABB / General ElectricSKLA36AT0800
| Brand | ABB / General Electric |
|---|---|
| Series | SKLC |
| Amperage | 800A |
| Poles | 3 |
| Mounting Style | Bolt-On |
| Voltage | 120VAC, 240VAC, 277VAC, 480VAC, 600VAC, 120/240VAC |
| Phase | 3 |
| AIC Rating | 100kA @ 120VAC, 100kA @ 240VAC, 65kA @ 277VAC, 65kA @ 480VAC, 42kA @ 600VAC, 100kA @ 120/240VAC |
| Amperage Range | 400-800A |
|---|
| Terminal Type | Lugs |
|---|---|
| For Use With | GE Spectra Series Panelboards, GE Spectra Series Switchboards, GE Motor Control Centers |
| Trip Technology | Electronic Trip |
|---|---|
| Trip Function Code | LSIG |
| Trip Function | Long-Time, Short-Time, Instantaneous, Ground Fault |
| Trip Adjustability | Adjustable |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Bell Alarm, Lug Kits, Rating Plugs, Padlock Attachment |
|---|---|
| Accessories | Breaker Harness Connector |
| Standards | CSA C22.2 No. 5, HACR, IEC 60947-2, UL 489 |
| Approval | CE, CSA, IEC, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Reverse Feed, Current Limiting, True RMS Sensing, Interchangeable Trip Unit, Modbus Communication, Waveform Capture |
This SK-frame breaker is designed for installation in GE Spectra Series panelboards, GE Spectra Series switchboards, and GE Motor Control Centers.
Yes, GE Spectra RMS circuit breakers require an interchangeable rating plug, such as the SRPK series, to establish the continuous current rating and activate the solid-state electronic trip unit.
The electronic trip unit allows licensed electricians to adjust Long-Time, Short-Time, Instantaneous, and Ground Fault settings. This enables precise coordination with other protective devices in the electrical distribution system.
ABB acquired General Electric's industrial circuit breaker division. Depending on the exact date of manufacture, the SKLC3608L4X6 may carry either the GE or ABB brand name, but the physical dimensions and technical specifications are identical.
This breaker accepts standard GE SK-frame lugs, such as the TCAL81 or TCAL125 series, depending on your specific wire size and whether you are using copper or aluminum conductors.
The ground fault setting on the LSIG trip unit detects low-level leakage currents to ground that might not trigger the standard overcurrent or short-circuit protections, helping to prevent equipment damage and electrical fires.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.