ABB / General ElectricSKLL3608L4XX
Quantity
New
Quantity
ABB / General ElectricSKLL3608L4XX
ABB / General ElectricSKLB36BB1200
ABB / General ElectricSKLB36BC1200
| Brand | ABB / General Electric |
|---|---|
| Part Number | SKLL36BD1200 |
| Series | SKLL |
| Amperage | 1200A |
| Poles | 3 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480VAC, 600VAC |
| Phase | 3 |
| AIC Rating | 100kA @ 240VAC, 65kA @ 480VAC, 42kA @ 600VAC |
| Amperage Range | 600-1200A |
|---|
| Frame Type | SKLL |
|---|---|
| Terminal Type | Lugs |
| For Use With | Spectra Series Switchboards, Spectra Series Power Panelboards, Motor Control Centers |
| Trip Technology | Electronic Trip |
|---|---|
| Trip Function Code | LSIG |
| Trip Function | Long-Time, Short-Time, Instantaneous, Ground Fault |
| Trip Adjustability | Adjustable |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Bell Alarm, Lug Kits, Padlock Attachment, Rating Plugs |
|---|---|
| Accessories | MicroVersaTrip Plus Trip Unit (LSIGT) |
| Standards | CSA C22.2 No. 5, IEC 60947-2, UL 489 |
| Approval | CE, CSA, IEC, UL |
| Temp Rating | -20C to 55C |
| Construction Features | 100% Rated, Current Limiting, HACR Rated, Reverse Feed, True RMS Sensing, Interchangeable Trip Unit, Visual Trip Indicator |
This Spectra RMS circuit breaker is designed for use in GE and ABB Spectra Series Switchboards, Spectra Series Power Panelboards, and Motor Control Centers.
Yes, this SK1200 frame breaker requires an SRPK series rating plug, such as the SRPK1200A1200, to establish its continuous current rating. The rating plug must be installed for the breaker to operate properly.
The SKLL36BD1200 accepts standard GE SK1200 frame lug kits. Common options include the TCAL124 and TCAL125 terminal kits, depending on your required wire size and conductor material.
It utilizes a solid state RMS sensing trip unit with LSIG functions. This provides adjustable Long-Time, Short-Time, Instantaneous, and Ground-Fault protection for precise system coordination.
ABB acquired GE Industrial Solutions in 2018. As a result, Spectra RMS breakers like the SKLL36BD1200 may carry either ABB or GE branding, but they remain identical in form, fit, and function.
Yes, the G in its LSIG trip function code indicates that it includes integrated ground fault protection, which helps prevent equipment damage and enhances safety during ground fault conditions.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.