ABB / General ElectricTHQB1130
Quantity
New
Quantity
ABB / General ElectricTHQB1130
ABB / General ElectricTHQB1130ST1
ABB / General ElectricTHQB1135
ABB / General ElectricTHQB1125
| Brand | ABB / General Electric |
|---|---|
| Series | THQB |
| Amperage | 30A |
| Poles | 1 |
| Mounting Style | Bolt-On |
| Voltage | 120/240VAC |
| Phase | 1 |
| AIC Rating | 10kA @ 120/240VAC |
| Frame Type | THQB |
|---|---|
| Terminal Type | Box Lugs |
| For Use With | GE A-Series Panelboards |
| Wire Gauge | 14-8 AWG (Cu), 12-8 AWG (Al) |
| Max Wire | 8 AWG |
| Min Wire | 14 AWG (Cu), 12 AWG (Al) |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Alarm Switch, Padlock Attachment |
|---|---|
| Accessories | Load Side Lugs Included |
| Standards | CSA C22.2 No. 5, HACR Rated, UL 489 |
| Approval | CSA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, HID Rated, Quick-Make/Quick-Break, Non-Interchangeable Trip |
This Q-Line miniature circuit breaker is designed for use in GE A-Series panelboards. It features a bolt-on connection that secures directly to the panel busbar, providing a rigid and reliable connection for commercial and industrial applications.
The HID designation means the breaker is UL listed for High Intensity Discharge lighting applications. It is specifically calibrated to handle the high inrush currents generated by metal halide, high-pressure sodium, and mercury vapor lamps without nuisance tripping.
Both are 30A, 1-pole bolt-on breakers for GE A-Series panels. However, the THQB1130HID includes a specific UL listing for High Intensity Discharge lighting. This makes it the required choice for commercial HID lighting circuits, whereas the standard THQB1130 is intended for general purpose branch circuit protection.
This breaker is equipped with standard box lugs that accept 14 to 8 AWG copper conductors or 12 to 8 AWG aluminum conductors. Always torque the terminal screws to the manufacturer specifications printed on the breaker label to ensure a secure connection.
Yes, GE THQB breakers in the 20A to 60A range are UL listed as HACR type. This makes this 30A breaker suitable for protecting heating, air conditioning, and refrigeration motor loads in addition to its HID lighting rating.
The THQB1130HID uses a fixed thermal element to provide long-time delay protection against sustained overloads. It also includes a fixed magnetic element that provides instantaneous tripping to quickly clear severe short circuits.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.