ABB / General ElectricTJJ436225WL
Quantity
Re-Certified
Quantity
ABB / General ElectricTJJ436225WL
ABB / General ElectricTJK436225WL
ABB / General ElectricTJK436225
ABB / General ElectricTJJ436225
| Brand | ABB / General Electric |
|---|---|
| Part Number | TJ236225 |
| Series | TJ |
| Amperage | 225A |
| Poles | 3 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480VAC, 600VAC, 250VDC, 500VDC |
| Phase | 3 |
| AIC Rating | 42kA @ 240VAC, 30kA @ 480VAC, 22kA @ 600VAC, 20kA @ 250VDC, 20kA @ 500VDC |
| Frame Type | TJ |
|---|---|
| Terminal Type | Lugs |
| For Use With | GE A-Series Panelboards, J-Line Enclosures, Motor Control Centers, Switchboards |
| Wire Gauge | (1) 6 AWG-600 kcmil (Cu/Al) or (2) 2/0 AWG-250 kcmil (Cu/Al) |
| Max Wire | 600 kcmil |
| Min Wire | 6 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Bell Alarm |
|---|---|
| Accessories | Line and Load Lugs Included |
| Standards | UL 489, NEMA AB-1 |
| Approval | CSA, UL |
| Temp Rating | 40C |
| Construction Features | Non-Interchangeable Trip |
This breaker is designed for use in GE A-Series panelboards, J-Line enclosures, motor control centers, and switchboards.
Yes, the legacy TJ frame can be replaced with an ABB Tmax XT4 circuit breaker by using the appropriate retrofit kit.
The included line and load lugs accept either one 6 AWG to 600 kcmil copper or aluminum wire, or two 2/0 AWG to 250 kcmil copper or aluminum wires per phase.
Yes, this breaker is rated for DC applications, providing an interrupting capacity of 20kAIC at both 250VDC and 500VDC.
No, this breaker features a non-interchangeable thermal magnetic trip unit with fixed thermal and fixed magnetic settings.
Available options include shunt trips, auxiliary switches, undervoltage releases, and bell alarms. Line and load lugs are already included.
This circuit breaker is calibrated for operation in a 40 degrees Celsius (104 degrees Fahrenheit) ambient environment.
This molded case circuit breaker meets UL 489 and NEMA AB-1 standards, and carries both UL and CSA approvals.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.