Designed for environments demanding high interrupting capacity, the Siemens QS2100HH delivers 100A main service protection with a 65 kAIC rating at 120/240V. It installs into Siemens Power Mod meter stacks, Uni-PAK metering systems, and legacy Murray load centers. Serving as an exact replacement for the discontinued MDH2100, this two-pole plug-on breaker ensures reliable performance.
Siemens Power Mod Meter Stacks, Uni-PAK Metering, Legacy Murray Load Centers
Wire Gauge
3 AWG - 300 kcmil (Cu/Al)
Max Wire
300 kcmil
Min Wire
3 AWG
Protection and operation
Trip Technology
Thermal Magnetic
Trip Function Code
LI
Trip Function
Long-Time, Instantaneous
Trip Adjustability
Fixed
Standards and features
Available Options
Padlock Attachment
Accessories
Load Side Lugs Included
Standards
UL 489, CSA C22.2 No. 5
Approval
CSA, UL
Temp Rating
40C
Construction Features
HACR Rated, High Interrupting Capacity, Reverse Feed, Main Breaker, Common Trip
Product FAQs
6 answers
Which metering equipment is compatible with the QS2100HH breaker?
This breaker is designed for use in Siemens Power Mod Meter Stacks, Uni-PAK Metering, and legacy Murray load centers. It fits directly into a 225A QS slot without requiring conversion kits or filler plates.
What is the acceptable wire size and torque specification for the QS2100HH?
The QS2100HH accepts 3 AWG to 300 kcmil copper or aluminum conductors. The terminal screws must be tightened to 250 lb-in of torque using a calibrated torque wrench.
What is the difference between the QS2100, QS2100H, and QS2100HH?
The difference is the short-circuit interrupting rating. The standard QS2100 is rated at 10kAIC, the QS2100H is rated at 22kAIC, and the QS2100HH provides a 65kAIC rating.
How does the side-wired design of the QS2100HH benefit installation?
The side-wired configuration optimizes wiring space within the meter stack. This eliminates the need for difficult S-bends and simplifies the connection process for large conductors.
Can the Siemens QS2100HH replace legacy Murray breakers?
Yes, Siemens QS series breakers are UL listed to replace legacy Murray breakers of the same frame size and specifications in compatible metering equipment.
What is the temperature rating for the conductors used with the QS2100HH?
The breaker terminals are designed and rated for use with 75 degrees Celsius copper or aluminum wire.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.