Configured for maximum system visibility, the Square D HGL36060U44X is a 60A, 3-pole electronic trip MCCB. It integrates seamlessly into motor control centers, switchboards, and PowerPacT H-Frame enclosures. This unit-mount breaker is equipped with a highly advanced Micrologic 6.2 A trip unit, offering adjustable LSIG (long-time, short-time, instantaneous, ground fault) protection. The built-in ammeter and true RMS sensing provide superior diagnostics and current-limiting performance.
CSA C22.2 No. 5, HACR, IEC 60947-2, NEMA AB 1, NOM-003-SCFI-2000, UL 489
Approval
CCC, CE, CSA, IEC, NOM, UL, UKCA
Temp Rating
-25C to 70C
Construction Features
Current Limiting, HACR Rated, True RMS Sensing, Ammeter
Product FAQs
8 answers
Can the HGL36060U44X be installed in an I-Line panelboard?
No, the HGL36060U44X is a unit-mount (feed-thru) breaker designed to be mounted with screws or brackets. If you need the I-Line plug-on equivalent for this 60A LSIG breaker, you will need part number HGA36060U44X.
What wire sizes are accepted by the standard lugs on the HGL36060U44X?
The factory-installed AL150HD mechanical lugs accept 14 AWG to 3/0 AWG aluminum or copper wire.
Can I use copper-only lugs on the HGL36060U44X?
Yes. While the standard AL150HD lugs are dual-rated for aluminum and copper, you can swap them for copper-only mechanical lugs (part number CU150HD) or copper compression lugs (part number CYA150HD) if your installation requires it.
What does the Micrologic 6.2 A trip unit provide on this breaker?
The 'A' in Micrologic 6.2 A stands for Ammeter, which provides integrated current measurement. The 6.2 indicates it offers LSIG (Long-Time, Short-Time, Instantaneous, and Ground-Fault) protection, allowing for precise coordination in your electrical system.
Are the trip settings adjustable on the HGL36060U44X?
Yes. The Micrologic 6.2 A electronic trip unit features adjustable dials for Long-Time pickup and delay, Short-Time pickup and delay, Instantaneous pickup, and Ground-Fault pickup and delay.
How does the ground-fault protection function on the HGL36060U44X?
The 'G' in the LSIG trip unit provides equipment ground-fault protection, not personnel protection (it is not a GFCI). If used in a 3-phase, 4-wire system, a neutral current transformer (CT) is required to properly monitor ground faults.
What does the 'G' in the HGL prefix indicate?
In the Square D PowerPacT nomenclature, the 'G' designates the interrupting rating tier. For this breaker, it provides 65kA at 240V, 35kA at 480V, and 18kA at 600V.
What enclosures or panels are compatible with the HGL36060U44X?
This feed-thru breaker is designed for use in industrial control panels, switchboards, motor control centers, and dedicated PowerPacT H-Frame enclosures.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 1 review.