| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | QBGFEP1030 |
| Series | QBGFEP |
| Amperage | 30A |
| Poles | 1 |
| Mounting Style | Bolt-On |
| Voltage | 120VAC |
| Phase | 1 |
| AIC Rating | 10kA @ 120VAC |
| Frame Type | BAB |
|---|---|
| Terminal Type | Box Lugs |
| For Use With | Eaton Pow-R-Line Panelboards |
| Wire Gauge | 14-4 AWG (Cu/Al) |
| Max Wire | 4 AWG |
| Min Wire | 14 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LIG |
| Trip Function | Long-Time, Instantaneous, Ground Fault |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Special Classification | GFEP |
|---|---|
| Available Options | Auxiliary Switch, Bell Alarm, Padlock Attachment |
| Accessories | Load Side Lugs Included |
| Standards | CSA C22.2 No. 5, UL 1053, UL 489 |
| Approval | CSA, HACR, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Non-Interchangeable Trip |
This Ground Fault Equipment Protection (GFEP) breaker features a 30 mA trip sensitivity. It is designed to protect equipment from damaging line-to-ground faults rather than providing Class A personnel protection.
This bolt-on breaker is designed for installation in Eaton Pow-R-Line panelboards, including the PRL1a, PRL2a, and PRL3a series that accept BAB-frame or Quicklag bolt-on breakers.
No. The QBGFEP1030 is a GFEP device with a 30 mA trip threshold. It does not provide the 5 mA Class A GFCI protection required by the National Electrical Code (NEC) for personnel safety in locations like bathrooms, kitchens, or pools.
GFEP breakers are typically installed to protect heat trace cables, snow-melting equipment, and outdoor de-icing systems. The 30 mA threshold prevents nuisance tripping that often occurs with 5 mA GFCIs in these applications.
The breaker is equipped with a pigtail neutral wire that must be connected directly to the neutral bar in the panelboard to ensure proper operation of the ground fault sensing circuitry.
No. The QBGFEP1030 features a bolt-on connection designed specifically for commercial Eaton Pow-R-Line panelboards. It cannot be used in residential load centers that require plug-on breakers.
Yes. In addition to ground fault equipment protection, it utilizes a thermal-magnetic trip unit to provide standard long-time (overload) and instantaneous (short-circuit) protection for the branch circuit.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.