Part of the Quicklag family, this 60A miniature circuit breaker provides reliable thermal-magnetic protection for commercial and industrial applications. The two-pole unit installs into Eaton Quicklag panelboards, control panels, and standard enclosures. It features a cable-in/cable-out design and can be DIN rail mounted using an adapter. Rated for 10kAIC at 120/240VAC, this panel mount breaker includes non-interchangeable trip functions. It is HACR rated for heating and cooling systems.
Control Panels, Enclosures, DIN Rail (with adapter), Eaton Quicklag Panelboards
Wire Gauge
14-4 AWG (Al/Cu)
Max Wire
4 AWG
Min Wire
14 AWG
Protection and operation
Trip Technology
Thermal Magnetic
Trip Function Code
LI
Trip Function
Long-Time, Instantaneous
Trip Adjustability
Fixed
Standards and features
Available Options
Padlock Attachment, DIN Rail Adapter
Accessories
Line and Load Lugs Included
Standards
CSA C22.2 No. 5, HACR, UL 489
Approval
CSA, UL
Temp Rating
40C
Construction Features
HACR Rated, Non-Interchangeable Trip
Product FAQs
6 answers
How does the Eaton QC2060 mount inside a panel or enclosure?
The QC2060 features a cable-in/cable-out (feed-thru) design. It can be base-mounted in control panels and enclosures, installed in Eaton Quicklag panelboards, or mounted to a standard 35mm DIN rail using an adapter.
What is the part number for the DIN rail adapter compatible with the QC2060?
To mount this breaker on a standard 35mm DIN rail, you will need the Eaton Quicklag DIN rail adapter, part number QCDINADAPT.
Can the QC2060 be used in DC voltage applications?
Yes, this thermal-magnetic breaker is rated for DC applications. It provides a 5kA interrupting capacity at 48VDC and a 3.8kA interrupting capacity at 62.5VDC.
What wire sizes are accepted by the box lugs on the QC2060?
The box lug terminals on this 60A breaker accept 14 AWG to 4 AWG aluminum or copper conductors.
Can the QC2060 be installed in standard residential load centers?
No, the QC series features a feed-thru, cable-in/cable-out design intended for control panels, enclosures, and Eaton Quicklag panelboards. It does not plug or bolt onto the busbars of standard residential load centers like the BR or CH series.
What type of protection does the LI trip function provide on this breaker?
The fixed thermal-magnetic trip unit includes Long-Time (L) and Instantaneous (I) functions. The thermal element provides long-time protection against sustained overloads, while the magnetic element provides instantaneous protection against short circuits.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 15 reviews.
My experience was great. I had the item quickly; and it was more reasonably priced than other places I checked. Not having to pay freight was an absolute bonus.