Operating as a high-capacity tenant main, the Eaton CCVH2100 supplies 100 amps of thermal-magnetic protection. This two-pole unit mount breaker is tailored for demanding metering centers. Contractors can install this model into Type ECC unit enclosures and standard Eaton group metering stacks. The included load-side lugs accept #2/0 AWG through 300 kcmil wiring. Carrying a 25kA interrupting capacity at 120/240VAC, this HACR-rated component upgrades legacy CCH2100 installations.
Eaton Group Metering Stacks (1MP, 1MM, 3MM), Type ECC Unit Enclosures
Wire Gauge
2/0 AWG - 300 kcmil (Cu/Al)
Max Wire
300 kcmil
Min Wire
2/0 AWG
Protection and operation
Trip Technology
Thermal Magnetic
Trip Function Code
LI
Trip Function
Long-Time, Instantaneous
Trip Adjustability
Fixed Thermal, Fixed Magnetic
Standards and features
Available Options
Shunt Trip, Auxiliary Switch, Alarm Switch
Accessories
Load Side Lugs
Standards
CSA C22.2 No. 5, UL 489
Approval
CSA, UL
Temp Rating
60C to 75C
Construction Features
HACR Rated, High Interrupting Capacity, Tenant Main
Product FAQs
6 answers
What is the difference between the Eaton CCVH2100 and the CCV2100?
The primary difference is the short circuit interrupting capacity. The CCVH2100 features a 25kAIC rating, while the standard CCV2100 is rated for 10kAIC. Both are 100A, 2-pole tenant main breakers that share the same physical footprint.
Can the CCVH2100 replace older Cutler-Hammer CCH frame breakers?
Yes, the CCVH2100 is the direct factory replacement for legacy 100A CCH2100 tenant main breakers. It fits the same metering stacks and enclosures as the obsolete models.
Which enclosures and metering centers are compatible with the CCVH2100?
This tenant main breaker is engineered for installation in Eaton Type ECC unit enclosures and standard Eaton group metering stacks, specifically the 1MP, 1MM, and 3MM modular series.
What size wire do the load lugs on the CCVH2100 accept?
The factory-installed load-side lugs accommodate 2/0 AWG through 300 kcmil copper or aluminum conductors.
Is the Eaton CCVH2100 HACR rated?
Yes, this circuit breaker carries an HACR rating, making it suitable for protecting heating, air conditioning, and refrigeration equipment circuits.
Are the trip settings on the CCVH2100 adjustable?
No, this breaker features fixed thermal and fixed magnetic trip settings for both long-time and instantaneous protection.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.