Eaton / Cutler-HammerFAZ-C32/3-NA
Quantity
New
Quantity
Eaton / Cutler-HammerFAZ-C32/3-NA
Eaton / Cutler-HammerFAZ-B15/3-NA
Eaton / Cutler-HammerFAZ-D30/3-NA
| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | FAZ-B30/3-NA |
| Series | FAZ |
| Amperage | 30A |
| Poles | 3 |
| Mounting Style | DIN Rail |
| Voltage | 480Y/277VAC, 96VDC |
| Phase | 3 |
| AIC Rating | 10kA @ 480Y/277VAC, 10kA @ 96VDC |
| Terminal Type | Box Lugs |
|---|---|
| For Use With | DIN Rail Panels, Industrial Control Panels |
| Wire Gauge | 18-6 AWG |
| Max Wire | 6 AWG |
| Min Wire | 18 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Curve | B |
| Trip Adjustability | Fixed |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Lockout Attachment, Busbar System |
|---|---|
| Standards | CSA C22.2 No. 5, IEC 60947-2, UL 489 |
| Approval | ABS, CE, CSA, DNV, Lloyd's, RoHS, UL, VDE |
| Temp Rating | -40C to 75C |
| Construction Features | Current Limiting, HACR Rated, Reverse Feed, Trip-Free Mechanism, Visual Trip Indicator |
The B-curve thermal-magnetic trip profile means the breaker is designed to trip instantaneously at 3 to 5 times its rated current. This makes it ideal for resistive loads or sensitive control circuitry where low levels of inrush current are expected.
Yes. The -NA suffix indicates that this breaker is UL 489 listed, meaning it is fully approved for branch circuit protection in North American applications, unlike UL 1077 supplementary protectors.
This breaker is designed to snap onto a standard 35mm DIN rail, which is commonly used in industrial control panels and automation enclosures.
The required fastening torque depends on the wire size used. For 18 to 12 AWG wire, torque to 21 lb-in. For 10 to 8 AWG, use 25 lb-in, and for 6 AWG wire, tighten to 36 lb-in.
Yes, it features a color-coded contact position indicator on the front. It displays red when the breaker is ON and green when it is OFF or tripped, allowing for quick visual diagnostics.
Yes, the FAZ-B30/3-NA features a current-limiting design. It interrupts fault currents within one-half cycle, which reduces the peak let-through energy and provides superior protection for downstream circuit components.
Yes, this breaker supports a feed-thru connection and can be reverse fed, allowing power to be supplied to either the top or bottom terminals depending on your panel layout.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.