| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | FAZ-C1/1-NA-SP |
| Series | FAZ-NA |
| Amperage | 1A |
| Poles | 1 |
| Mounting Style | DIN Rail |
| Voltage | 277VAC, 48VDC |
| Phase | 1 |
| AIC Rating | 10kA @ 277VAC, 10kA @ 48VDC |
| Frame Type | FAZ |
|---|---|
| Terminal Type | Box Lugs |
| For Use With | DIN Rail Systems, Industrial Control Panels |
| Wire Gauge | 18-6 AWG (1 wire), 18-10 AWG (2 wires) |
| Max Wire | 6 AWG |
| Min Wire | 18 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Curve | C |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Auxiliary Switch, Shunt Trip, Undervoltage Release, Alarm Switch, Lockout Attachment, Busbar System |
|---|---|
| Standards | CSA C22.2 No. 5, IEC 60947-2, RoHS, UL 489 |
| Approval | ABS, CE, CSA, cULus, DNV, IEC, Lloyd's, RoHS, UL, VDE |
| Temp Rating | -25C to 75C |
| Construction Features | Current Limiting, HACR Rated, Reverse Feed, Trip-Free Mechanism, Visual Trip Indicator |
The C curve indicates a medium magnetic trip point of 5 to 10 times the rated current. It is designed for applications with medium inrush currents, such as small transformers, pilot devices, control circuits, and lighting.
Yes, the FAZ-NA series is UL 489 listed for branch circuit protection. It can also be used in applications where UL 1077 supplementary protectors are permitted.
This miniature circuit breaker mounts directly onto a standard 35mm DIN rail, making it suitable for industrial control panels and feeder applications.
Yes, it features a current limiting design that interrupts fault currents within one half cycle. This reduces the peak let-through energy to protect the circuit from damage.
Yes, power to this circuit breaker can be fed from either the line or the load side.
The SP suffix indicates that the breaker comes in a single package. The core breaker is identical to the standard FAZ-C1/1-NA.
The screw clamp terminals accept 18 to 6 AWG for a single wire, or 18 to 10 AWG when connecting two wires.
Yes, it features a color-coded indicator that provides immediate visual confirmation of the device status, showing red for ON and green for OFF.
Yes, the FAZ-NA series utilizes a trip-free design. The breaker will trip under fault conditions even if the handle is held in the ON position.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.