| Brand | ABB / General Electric |
|---|---|
| Part Number | TMQD22070 |
| Series | TMQD |
| Amperage | 70A |
| Poles | 2 |
| Mounting Style | Bolt-On |
| Voltage | 120/240VAC |
| Phase | 1 |
| AIC Rating | 100kA @ 120/240VAC |
| Frame Type | TMQD |
|---|---|
| Terminal Type | Lugs |
| For Use With | GE Meter Mod Meter Stacks, GE Panelboards |
| Wire Gauge | 6 AWG - 1/0 AWG (Cu/Al) |
| Max Wire | 1/0 AWG |
| Min Wire | 6 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release |
|---|---|
| Accessories | Load Side Lugs |
| Standards | CSA C22.2 No. 5, UL 489 |
| Approval | CSA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Extra High Interrupting Capacity, Non-Interchangeable Trip, Tenant Main |
This bolt-on breaker is primarily used as a tenant main disconnect in GE Meter Mod meter stacks. It is also compatible with GE panelboards configured for TMQD frame breakers.
The factory-installed load side lugs accept 6 AWG to 1/0 AWG wire. They are rated for use with both copper (Cu) and aluminum (Al) conductors.
The 100kAIC rating indicates that the breaker can safely interrupt up to 100,000 amps of fault current at 240V. This extra-high interrupting capacity makes it suitable for commercial and industrial applications with high available fault currents.
These breakers share the same physical dimensions and bolt-on mounting, but they have different short circuit interrupting ratings. The TQD is rated for 10kAIC, the THQD is rated for 22kAIC, and the TMQD is rated for 100kAIC at 240V. You must use a breaker that meets or exceeds the available fault current of your electrical system.
It utilizes a bolt-on connection to secure directly to the panel busbar. This provides a highly reliable, vibration-resistant electrical connection compared to standard plug-in breakers.
The LI (Long-Time and Instantaneous) designation means the breaker uses a thermal-magnetic trip unit. The thermal element provides long-time delay protection against continuous overloads, while the magnetic element provides instantaneous tripping during severe short circuits.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.