A versatile solution for industrial switchboards, the Siemens 3VA5140-4ED21-0AA0 is a 2-pole, 40A molded case circuit breaker. It is equipped with fixed thermal and fixed magnetic trip functions for precise LI protection. This breaker installs into modern Siemens 3VA panelboards and can replace discontinued ED42B040 units in legacy P1 and P2 panels when paired with the proper mounting kit. It delivers a 25kAIC rating at 480VAC and features a current-limiting, trip-free mechanism.
Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Motor Operator, Rotary Handle, Padlock Attachment, DIN Rail Adapter, Lug Kits
Accessories
None (No Lugs Included)
Standards
IEC 60947-2, UL 489, CSA C22.2 No. 5, HACR Rated
Approval
ABS, CE, CSA, EAC, IEC, UL, VDE
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Reverse Feed, Current Limiting, Non-Interchangeable Trip, Common Trip, Trip-Free Mechanism, Quick-Make/Quick-Break
Product FAQs
7 answers
What legacy Siemens breaker does the 3VA5140-4ED21-0AA0 replace?
This 3VA5 series breaker is the modern replacement for the discontinued ED42B040. To install it in legacy Siemens P1 or P2 panelboards, you will need the appropriate mounting adapter kit.
Which Siemens panelboards accept this 2-pole breaker?
It installs directly into modern Siemens 3VA panelboards and switchboards. It is also compatible with Siemens P1 and P2 panelboards when used with the correct mounting adapter.
Can the 3VA5140-4ED21-0AA0 be reverse fed?
Yes. Like all Siemens 3VA5 thermal-magnetic circuit breakers, this unit is UL listed for reverse feed applications, which allows for flexible installation orientations.
Is this 40A circuit breaker HACR rated?
Yes, it carries an HACR rating, meaning it is certified for use in heating, air conditioning, and refrigeration applications.
What type of trip unit does this breaker use?
It is equipped with a TM210 thermal-magnetic trip unit. This provides fixed long-time (Ir) and fixed instantaneous (Ii) protection for reliable overload and short-circuit defense.
How is this breaker rated for direct current (DC) applications?
This 2-pole breaker is suitable for DC systems up to 250VDC. When applied on 250VDC systems, it provides an interrupting rating of 50kA.
What frame size is this 40A breaker built on?
It is built on the Siemens 3VA51 frame, which supports a maximum capacity of 125 amps.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 4.8 out of 5 based on 8 reviews.