Delivering 200 amps of reliable power control, the Siemens FXD62B200L is a 2-pole MCCB from the Sentron family. It utilizes thermal-magnetic technology to provide essential LI protection. This unit mount breaker installs into Siemens P1, P2, and P3 panelboards. Unlike the standard version, it includes factory-installed line and load lugs accepting 6 AWG to 350 kcmil wire. Capable of interrupting 35kA at 480VAC, it features an adjustable magnetic trip and is HACR and reverse feed rated.
What panelboards are compatible with the FXD62B200L?
This breaker is designed for installation in Siemens Sentron P1, P2, and P3 panelboards, as well as compatible switchboards and standalone enclosures.
What is the difference between the FXD62B200 and the FXD62B200L?
The L suffix indicates that the FXD62B200L comes with factory installed line and load lugs (catalog number TA1FD350A). The standard FXD62B200 is supplied without lugs.
How does the FXD6 series differ from the FD6 series?
The primary difference is the trip unit design. FXD6 breakers have a non-interchangeable fixed trip unit. FD6 breakers feature an interchangeable thermal magnetic trip unit. Both share the same FD frame footprint and interrupting capacities.
What is the magnetic trip adjustment range for this 200A breaker?
The adjustable magnetic trip range for the 200A FXD62B200L is 900A to 2000A.
Can the FXD62B200L be reverse fed?
Yes, this thermal magnetic molded case circuit breaker is reverse feed rated. It can be wired with the line connections on either the top or bottom terminals.
What wire sizes do the included lugs accept?
The factory installed TA1FD350A lugs accept 6 AWG to 350 kcmil copper or aluminum wire.
Is the FXD62B200L suitable for HVAC applications?
Yes, this breaker is HACR rated, meaning it is approved for use with heating, air conditioning, and refrigeration equipment.
What are the standard safety practices for installing this breaker?
Always disconnect and lock out all power sources before installation. Verify that the panelboard is marked to accept FXD6 or FD frame breakers, and ensure proper torque is applied to the lug screws as specified by the manufacturer to prevent overheating.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.