Built for demanding industrial environments, the Square D KAL36110-1039 provides robust thermal-magnetic protection. This 3-pole, 110A breaker is designed to safeguard commercial electrical distribution systems. The unit mount configuration fits securely into Square D motor control centers and enclosures. For facilities updating their infrastructure, this legacy K-Frame model is replaced by the PowerPacT HGL36110. Equipped with a 12VDC shunt trip, it allows for automated circuit interruption.
Shunt Trip (12VDC) (Factory Installed), Line and Load Lugs Included
Standards
CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489
Approval
CE, CSA, HACR, IEC, UL
Temp Rating
40C
Construction Features
HACR Rated, Trip-Free Mechanism, Common Trip
Product FAQs
6 answers
What is the modern replacement for the KAL36110-1039?
The legacy K-Frame KAL36110-1039 is replaced by the Square D PowerPacT HGL36110. Because the -1039 suffix indicates a 12VDC shunt trip, you will need to add a compatible 12VDC shunt trip accessory to the new H-Frame breaker to maintain remote tripping functionality.
What does the -1039 suffix indicate on this KAL breaker?
The -1039 suffix designates a factory-installed 12VDC shunt trip. This allows the circuit breaker to be tripped remotely by applying a 12VDC control voltage signal, which is commonly used for emergency stops or automated load shedding.
How is the KAL36110-1039 installed in a system?
This is a unit-mount, feed-thru circuit breaker. It bolts directly to the backpan of legacy Square D enclosures, switchboards, or motor control centers, rather than plugging into an I-Line bus.
How does the adjustable magnetic trip work on this 110A breaker?
While the thermal overload protection is fixed at 110A, the magnetic instantaneous trip is adjustable. This allows panel builders to fine-tune the short-circuit response to coordinate with downstream devices and prevent nuisance tripping from motor inrush currents.
Can I install this K-Frame breaker in an I-Line panelboard?
No, the KAL36110-1039 is a unit-mount breaker designed for individual enclosures or backpan mounting. For an I-Line panelboard, you would need an I-Line specific breaker, such as the legacy KA or modern PowerPacT HGA series.
Is the KAL36110-1039 suitable for DC applications?
Yes, this thermal-magnetic breaker is rated for use in DC systems up to 250VDC, where it provides an interrupting capacity of 10kA. It can be utilized in battery-string or charger feeder applications, provided the system voltage does not exceed 250VDC.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 3 reviews.