Engineered for demanding commercial environments, this 800A electronic trip circuit breaker provides reliable power distribution and monitoring. Designed specifically for Square D I-Line panelboards and switchboards, the plug-on jaw connection simplifies phase balancing and installation. A built-in Micrologic 6.0A trip unit supplies true RMS sensing, an integrated ammeter, and configurable LSIG settings to ensure precise fault coordination across your electrical system.
Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Motor Operator, Communication Module
Accessories
Micrologic 6.0A Trip Unit
Standards
CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489
Approval
CE, CSA, IEC, NOM, UL
Temp Rating
-25C to 70C
Construction Features
80% Rated, HACR Rated, True RMS Sensing, Ammeter
Product FAQs
9 answers
What panelboards are compatible with the PGA36080U44A?
This breaker is designed specifically for installation in Square D I-Line panelboards and switchboards.
What does the U44A suffix mean on this Square D breaker?
The U44A designation indicates the breaker is equipped with a Micrologic 6.0A electronic trip unit. This provides an integrated ammeter and adjustable Long-Time, Short-Time, Instantaneous, and Ground-Fault (LSIG) protection.
What type of terminations are standard on the PGA36080U44A?
This breaker features an I-Line plug-on jaw connection on the line side and mechanical lugs on the load side.
What wire sizes do the load-side lugs accept?
The standard load lugs accommodate three 3/0 AWG to 500 kcmil aluminum or copper conductors per phase.
Is the PGA36080U44A rated for 100 percent continuous current?
No, this specific catalog number is standard-rated for 80 percent continuous current. Square D models rated for 100 percent continuous current typically include the letter C in the catalog number, such as PGA36080CU44A.
Does this breaker provide equipment ground-fault protection?
Yes, the included Micrologic 6.0A trip unit features adjustable ground-fault protection, allowing for precise coordination in systems requiring equipment ground-fault sensing.
Can the trip unit on the PGA36080U44A be swapped in the field?
Yes, PowerPacT P-Frame breakers equipped with Micrologic trip units allow for field interchangeability. The trip unit can be upgraded or replaced if system protection or monitoring requirements change.
How does the I-Line connection simplify installation?
The I-Line plug-on design allows the breaker to mount directly onto the panelboard bus with a jaw connection. This eliminates the need for line-side cabling and makes phase balancing much faster for panel builders.
How customizable is the protection on the Micrologic 6.0A trip unit?
The trip unit provides fully adjustable settings for Long-Time, Short-Time, Instantaneous, and Ground-Fault pickup and delay, allowing electricians to achieve precise coordination with other devices in the electrical system.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.