Schneider Electric / Square DPJL36120U44A
Quantity
New
Quantity
Schneider Electric / Square DPJL36120U44A
| Brand | Square D |
|---|---|
| Part Number | PJL36080CU31A |
| Series | PJL |
| Amperage | 800A |
| Poles | 3 |
| Mounting Style | Unit Mount |
| Voltage | 240VAC, 480VAC, 600VAC |
| Phase | 3 |
| AIC Rating | 100kA @ 240VAC, 65kA @ 480VAC, 25kA @ 600VAC |
| Frame Type | PJL |
|---|---|
| Terminal Type | Lugs |
| For Use With | Square D QED Switchboards, Motor Control Centers, PowerPacT P-Frame Enclosures |
| Wire Gauge | (3) 3/0 AWG - 500 kcmil (Al/Cu) |
| Max Wire | 500 kcmil |
| Min Wire | 3/0 AWG |
| Trip Technology | Electronic Trip |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Adjustable |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Motor Operator, Rotary Handle, Padlock Attachment |
|---|---|
| Accessories | Micrologic 3.0 Trip Unit |
| Standards | CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489 |
| Approval | CE, CSA, IEC, NOM, UL |
| Temp Rating | -25C to 70C |
| Construction Features | 100% Rated, HACR Rated, True RMS Sensing |
The C indicates this breaker is 100 percent rated. This means it can carry its full 800A continuous current capacity without the standard 80 percent derating required for conventional circuit breakers.
This model features a standard Micrologic 3.0 electronic trip unit. It provides adjustable long-time and instantaneous protection, commonly referred to as LI functions.
Yes. The Micrologic 3.0 solid state trip unit allows you to adjust both the long-time pickup and instantaneous settings to ensure precise system coordination.
No. The PJL36080CU31A is a unit mount, feed-thru breaker equipped with mechanical lugs on both the line and load sides. It does not have the plug-on jaws required for I-Line distribution gear.
The factory installed lugs accept three 3/0 AWG to 500 kcmil aluminum or copper conductors per phase.
Yes, PowerPacT P-frame unit mount breakers can serve as drop-in upgrades for legacy Square D PE800 or PE frame models in most switchboard applications.
No. The U31A designation indicates a Micrologic 3.0 trip unit, which offers only long-time and instantaneous (LI) protection. It does not include integral ground fault functions.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.