| Brand | Square D |
|---|---|
| Series | PJL |
| Amperage | 1200A |
| Poles | 3 |
| Mounting Style | Unit Mount |
| Voltage | 240VAC, 480VAC, 600VAC |
| Phase | 3 |
| AIC Rating | 100kA @ 240VAC, 65kA @ 480VAC, 25kA @ 600VAC |
| Frame Type | P |
|---|---|
| Terminal Type | Lugs |
| For Use With | Square D QED Switchboards, Model 6 Motor Control Centers, PowerPacT P-Frame Enclosures |
| Wire Gauge | (4) 3/0 AWG - 500 kcmil (Al/Cu) |
| Max Wire | 500 kcmil |
| Min Wire | 3/0 AWG |
| Trip Technology | Electronic Trip |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Adjustable |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Motor Operator, Padlock Attachment |
|---|---|
| Accessories | Micrologic 3.0 Trip Unit |
| Standards | CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489 |
| Approval | CE, CSA, IEC, NOM, UL |
| Temp Rating | -25C to 70C |
| Construction Features | 80% Rated, HACR Rated, True RMS Sensing, Interchangeable Trip Unit, Quick-Make/Quick-Break, Trip-Free Mechanism |
This unit-mount breaker is designed for use in Square D QED switchboards, Model 6 motor control centers, and PowerPacT P-Frame enclosures.
No, the PJL36120U31A is a unit-mount breaker designed to be bolted into place. It is not compatible with I-Line panelboards, which require plug-on I-Line style breakers.
It features a Micrologic 3.0 electronic trip unit, which provides adjustable long-time and instantaneous (LI) protection for precise circuit coordination.
Yes, the Micrologic 3.0 trip unit allows you to adjust the long-time pickup settings to match your specific load requirements and ensure proper system coordination.
The factory-installed lugs accept four 3/0 AWG to 500 kcmil aluminum or copper conductors per phase.
Yes, the included lugs are dual-rated for both aluminum and copper conductors, providing flexibility during installation.
The U31A suffix indicates that the breaker is equipped with a Micrologic 3.0 standard electronic trip unit featuring long-time and instantaneous (LI) trip functions.
No, the Micrologic 3.0 LI trip unit does not include ground fault protection. If ground fault protection is required, a breaker with a Micrologic 6.0 LSIG trip unit is necessary.
This breaker has a standard 80 percent continuous current rating, meaning the continuous load should not exceed 960 amps.
It is a unit-mount breaker, meaning it bolts directly to the bus or mounting pan in compatible switchboards and enclosures, rather than plugging onto a bus stack.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.