ABB / General ElectricTHQL2120GF1
Quantity
New
Quantity
ABB / General ElectricTHQL2120GF1
ABB / General ElectricTHQL2120GFT
ABB / General ElectricTHQL2125GFT
ABB / General ElectricTHQL2130GFT
| Brand | ABB / General Electric |
|---|---|
| Part Number | THQL2115GFT |
| Series | THQL |
| Amperage | 15A |
| Poles | 2 |
| Mounting Style | Plug-On |
| Voltage | 120/240VAC |
| Phase | 1 |
| AIC Rating | 10kA @ 120/240VAC |
| Frame Type | THQL |
|---|---|
| Terminal Type | Box Lugs |
| For Use With | GE Q-Line Load Centers, GE PowerMark Gold Load Centers |
| Wire Gauge | 14-8 AWG (Cu), 12-8 AWG (Al) |
| Max Wire | 8 AWG |
| Min Wire | 14 AWG (Cu), 12 AWG (Al) |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LIG |
| Trip Function | Long-Time, Instantaneous, Ground Fault |
| Trip Adjustability | Fixed |
| Special Classification | GFCI |
|---|---|
| Available Options | Padlock Attachment |
| Accessories | Self-Test Feature |
| Standards | HACR, NEMA AB 1, UL 489, UL 943 |
| Approval | CSA, UL |
| Temp Rating | 60C to 75C |
| Construction Features | Self-Test, HACR Rated, Common Trip, Quick-Make/Quick-Break |
This breaker is designed for use in GE Q-Line, GE PowerMark Gold, and ABB ReliaHome load centers that accept 1-inch plug-in breakers.
Yes, the GFT suffix indicates it includes an automatic self-test function. This continuously monitors the internal electronics to ensure the Class A 5mA ground fault protection remains fully operational.
The THQL2115GFT utilizes a pigtail neutral wire that must be connected directly to the neutral bus bar in the load center to ensure proper ground fault detection.
Yes, this self-testing model serves as a direct replacement for the older, discontinued THQL2115GF breaker. It fits the same physical footprint while offering upgraded diagnostics to meet current NEC standards.
It features Class A ground fault protection, meaning it is designed to trip when it detects a ground fault leakage current of 5mA.
A 2-pole 15A GFCI breaker is commonly used for 240V circuits requiring ground fault protection, such as pool pumps, spa equipment, or specific outdoor equipment, in accordance with NEC requirements.
The LIG designation means the breaker provides Long-Time (thermal overload), Instantaneous (short circuit), and Ground Fault protection in a single unit.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.