ABB / General ElectricTHQL2140GF1
Quantity
New
Quantity
ABB / General ElectricTHQL2140GF1
ABB / General ElectricTHQL2140GFT
ABB / General ElectricTHQL2140GFT2
ABB / General ElectricTHQL2140GF
| Brand | ABB / General Electric |
|---|---|
| Series | THQL |
| Amperage | 35A |
| Poles | 2 |
| Mounting Style | Plug-On |
| Voltage | 120/240VAC |
| Phase | 1 |
| AIC Rating | 10kA @ 120/240VAC |
| Frame Type | THQL |
|---|---|
| Terminal Type | Box Lugs |
| For Use With | GE PowerMark Gold Load Centers, GE A-Series Panelboards, ABB ReliaHome Load Centers |
| Wire Gauge | 8-3 AWG (Cu), 8-3 AWG (Al) |
| Max Wire | 3 AWG |
| Min Wire | 8 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LIG |
| Trip Function | Long-Time, Instantaneous, Ground Fault |
| Trip Adjustability | Fixed |
| Special Classification | GFCI |
|---|---|
| Available Options | Padlock Attachment, Auxiliary Switch |
| Accessories | Self-Test Feature (Internal) |
| Standards | HACR, UL 489, UL 943 |
| Approval | CSA, UL |
| Temp Rating | 60C to 75C |
| Construction Features | HACR Rated, Common Trip, Quick-Make/Quick-Break, Self-Test |
The THQL2135GFT2 features a pigtail neutral. The coiled white pigtail wire must be connected directly to the panel's neutral bus bar for the ground fault protection to function properly. The load neutral connects to the breaker's designated load neutral lug.
For straight 240V loads that do not require a neutral, you do not need to connect a wire to the breaker's load neutral lug. However, the breaker's white pigtail must still be connected to the panel's neutral bus bar to power the GFCI mechanism.
This breaker provides Class A 5mA ground fault personnel protection. It includes an internal self-test feature to continuously verify the GFCI circuitry is functioning correctly.
ABB acquired GE Industrial Solutions, so this breaker may arrive with either ABB or GE branding. The product is identical in form, fit, and function regardless of the label.
Yes, the THQL2135GFT2 is the direct modern replacement for the older THQL2135GFT model. It adds continuous self-test capabilities while maintaining the same physical footprint.
THQL breakers require a full 1-inch space per pole. They cannot be installed in half-inch slots designed exclusively for THQP tandem breakers, though many GE PowerMark Gold panels accept both types in designated positions.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.