ABB / General ElectricTHQL2160ST1
Quantity
New
Quantity
ABB / General ElectricTHQL2160ST1
ABB / General ElectricTHQL2140ST1
ABB / General ElectricTHQL2170ST1
ABB / General ElectricTHQL2130ST1
| Brand | ABB / General Electric |
|---|---|
| Series | THQL |
| Amperage | 50A |
| Poles | 2 |
| Mounting Style | Plug-On |
| Voltage | 120/240VAC |
| Phase | 1 |
| AIC Rating | 10kA @ 120/240VAC |
| Frame Type | THQL |
|---|---|
| Terminal Type | Box Lugs |
| For Use With | GE PowerMark Gold Load Centers, GE A-Series Panelboards |
| Wire Gauge | 8-3 AWG (Cu/Al) |
| Max Wire | 3 AWG |
| Min Wire | 8 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed |
| Available Options | Padlock Attachment, Auxiliary Switch |
|---|---|
| Accessories | Shunt Trip |
| Standards | CSA C22.2 No. 5, UL 489, HACR |
| Approval | CSA, UL |
| Temp Rating | 10C to 50C |
| Construction Features | HACR Rated, Common Trip, Quick-Make/Quick-Break |
This plug-on breaker is designed for use in GE PowerMark Gold load centers and GE A-Series panelboards that accept 1-inch THQL series breakers.
The ST1 suffix means this breaker is equipped with a factory-installed 120V shunt trip mechanism. This allows the breaker to be tripped remotely for emergency shutdowns or automated control systems.
ABB acquired GE Industrial Solutions in 2018. Depending on the manufacturing date, the THQL2150ST1 may be branded as either ABB or GE, but the physical breaker, fit, and function remain identical.
The 120V shunt trip mechanism includes a pigtail wire that connects to your external control circuit, allowing a remote voltage signal to open the breaker contacts.
No. THQL breakers are plug-on style, while THQB breakers are bolt-on style typically used in commercial lighting panels. They are not interchangeable.
As a 2-pole Q-Line breaker, it requires two standard 1-inch spaces in a compatible GE load center.
The shunt trip allows for remote disconnection of power. It is commonly used to tie the breaker into fire alarm systems, emergency stop buttons, or other automated safety controls that require immediate circuit de-energization.
The LI designation indicates the breaker uses a thermal magnetic trip unit with Long-Time (thermal) protection for overloads and Instantaneous (magnetic) protection for short circuits.
No. This is a standard thermal magnetic breaker providing overload and short-circuit protection. It does not include ground fault or arc fault protection.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.