ABB / General ElectricTHQL1120AF2
Quantity
New
Quantity
ABB / General ElectricTHQL1120AF2
ABB / General ElectricTHQL1120AF2S
ABB / General ElectricTHQL1120AFP2
ABB / General ElectricTHQL1115AF
| Brand | ABB / General Electric |
|---|---|
| Series | THQL |
| Amperage | 20A |
| Poles | 1 |
| Mounting Style | Plug-On |
| Voltage | 120/240VAC |
| Phase | 1 |
| AIC Rating | 10kA @ 120/240VAC |
| Frame Type | THQL |
|---|---|
| Terminal Type | Box Lugs |
| For Use With | GE PowerMark Gold Load Centers (Plug-on Neutral), ABB ReliaHome Load Centers (Plug-on Neutral) |
| Wire Gauge | 14-8 AWG (Cu), 12-8 AWG (Al) |
| Max Wire | 8 AWG |
| Min Wire | 14 AWG (Cu), 12 AWG (Al) |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Special Classification | AFCI |
|---|---|
| Available Options | Padlock Attachment, Shunt Trip, Auxiliary Switch |
| Standards | HACR, NEMA AB 1, UL 1699, UL 489 |
| Approval | CSA, UL |
| Temp Rating | 60C to 75C |
No. This breaker features a plug-on neutral (PON) clip that mounts directly to the neutral bus bar in compatible panels. This design eliminates the need to route and terminate a separate pigtail wire in the panel gutter.
It only fits GE PowerMark Gold and ABB ReliaHome load centers specifically equipped with a plug-on neutral bus. It cannot be installed in legacy panels that lack PON architecture.
The P in THQL1120PAF2 indicates a plug-on neutral design for PON-equipped load centers. The THQL1120AF2 lacks this clip and instead relies on a standard neutral pigtail wire, making it necessary for older, non-PON panels.
Yes. It is a Combination Arc-Fault Circuit Interrupter (CAFCI), meaning it detects both series and parallel arcing conditions to meet NEC 210.12 requirements for 120V branch circuits in dwelling units.
The load neutral wire from the branch circuit lands directly on the breaker's dedicated load neutral terminal. The breaker then completes the neutral return path to the panel internally through its PON clip.
No. Like standard miniature circuit breakers, it is rated for 80 percent continuous load. Continuous loads operating for three hours or more should not exceed 16 amps on this 20-amp device.
This specific breaker is rated for a maximum of 10 kAIC at 120/240V. If the electrical service requires a higher interrupting capacity, you must specify a different breaker series, such as the THHQL1120PAF2, which offers a 22 kAIC rating.
Yes. For 120V branch circuits requiring arc-fault protection upgrades, it replaces standard 1-pole 20A THQL breakers, provided the existing load center has a compatible plug-on neutral bus.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.