ABB / General ElectricTEYD1035B
Quantity
New
Quantity
ABB / General ElectricTEYD1035B
ABB / General ElectricTEYD1020B
ABB / General ElectricTEYD1015B
ABB / General ElectricTEYD2040B
| Brand | ABB / General Electric |
|---|---|
| Series | TEYD |
| Amperage | 40A |
| Poles | 1 |
| Mounting Style | Bolt-On |
| Voltage | 120VAC, 277VAC, 125VDC, 120/240VAC |
| Phase | 1 |
| AIC Rating | 65kA @ 120VAC, 25kA @ 277VAC, 10kA @ 125VDC, 65kA @ 120/240VAC |
| Frame Type | TEYD |
|---|---|
| Terminal Type | Lugs |
| For Use With | GE A-Series Panelboards |
| Wire Gauge | 10-4 AWG (Cu/Al) |
| Max Wire | 4 AWG |
| Min Wire | 10 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Padlock Attachment |
|---|---|
| Accessories | Load Side Lugs |
| Standards | CSA C22.2 No. 5, NEMA AB 1, UL 489 |
| Approval | CSA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, HID Rated, Quick-Make/Quick-Break, Non-Interchangeable Trip |
The TEYD1040B is a bolt-on circuit breaker designed specifically for use in GE A-Series panelboards. It is not compatible with standard residential load centers or DIN rail systems.
These breakers share the same 1-inch per pole physical footprint and mount in GE A-Series panelboards, but they feature different short-circuit interrupting ratings at 480Y/277VAC. The standard TEY is rated at 14kAIC, the TEYF at 18kAIC, and the TEYD at 25kAIC.
For the factory-installed lugs on the TEYD1040B, the required torque depends on the wire gauge: 35 in-lb for 10 AWG, 40 in-lb for 8 AWG, and 45 in-lb for 6 to 4 AWG wire.
Yes, this breaker is rated for use in direct current applications up to 125VDC with an interrupting capacity of 10kAIC.
Yes, this breaker is UL listed for both HACR (Heating, Air Conditioning, and Refrigeration) and HID (High Intensity Discharge) lighting applications.
No, the TEYD1040B is a bolt-on circuit breaker that requires a bolted connection to the panelboard busbar. It cannot be mounted on a DIN rail.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.