Eaton / Cutler-HammerFAZ-B15/3-NA
Quantity
New
Quantity
Eaton / Cutler-HammerFAZ-B15/3-NA
Eaton / Cutler-HammerFAZ-B30/3-NA
Eaton / Cutler-HammerFAZ-C32/3-NA
| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | FAZ-B4/3-NA |
| Series | FAZ |
| Amperage | 4A |
| Poles | 3 |
| Mounting Style | DIN Rail |
| Voltage | 480Y/277VAC, 96VDC |
| Phase | 3 |
| AIC Rating | 10kA @ 480Y/277VAC, 10kA @ 96VDC |
| Terminal Type | Box Lugs |
|---|---|
| For Use With | DIN Rail Systems, Industrial Control Panels |
| Wire Gauge | 18-6 AWG (1 wire), 18-10 AWG (2 wires) |
| Max Wire | 6 AWG |
| Min Wire | 18 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Curve | B |
| Trip Adjustability | Fixed |
| Available Options | Auxiliary Switch, Alarm Switch, Shunt Trip, Undervoltage Release, Padlock Attachment, Busbar System |
|---|---|
| Standards | CSA C22.2 No. 5, IEC 60947-2, UL 489 |
| Approval | ABS, CE, CSA, cULus, DNV, IEC, Lloyd's, SWD, UL, VDE |
| Temp Rating | -25C to 75C |
| Construction Features | Current Limiting, HACR Rated, Reverse Feed, Common Trip, Trip-Free Mechanism, RoHS Compliant |
The B-curve magnetic trip point is set between 3 and 5 times the rated current. This makes it ideal for protecting highly resistive loads, control circuits, and applications where low levels of inrush current are expected, such as PLCs and sensitive control instrumentation.
Yes. The -NA suffix indicates this breaker is UL 489 listed for branch circuit protection, unlike standard FAZ breakers which are UL 1077 supplementary protectors. It can be used for feeder and branch circuits, motor control circuits, and HACR equipment.
Yes, this breaker supports reverse feed configurations. The line and load connections can be wired to either the top or bottom terminals without affecting the protective functions of the device.
The required torque depends on the wire size used. For 18 to 12 AWG wire, torque to 21 lb-in. For 10 to 8 AWG wire, torque to 25 lb-in. For 6 AWG wire, torque to 36 lb-in.
Yes, the FAZ-NA series accepts snap-on accessories including auxiliary contacts, alarm switches, shunt trips, and undervoltage releases. These mount directly to the side of the breaker without requiring special tools.
Yes, it features a current-limiting design that interrupts fault currents within one-half cycle. This rapid response reduces the peak let-through energy, providing superior protection for downstream components.
Yes, the FAZ-B4/3-NA features a trip-free design. The breaker contacts will open under fault conditions even if the operating handle is physically held in the ON position.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.