Eaton / Cutler-HammerGHB3020S1
Quantity
New
Quantity
Eaton / Cutler-HammerGHB3020S1
Eaton / Cutler-HammerGHB3025S1
Eaton / Cutler-HammerGHB3015S1
Eaton / Cutler-HammerGHB3030S1
| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | GHB3020S2 |
| Series | GHB |
| Amperage | 20A |
| Poles | 3 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480Y/277VAC, 125/250VDC |
| Phase | 3 |
| AIC Rating | 65kA @ 240VAC, 14kA @ 480Y/277VAC, 14kA @ 125/250VDC |
| Frame Type | G |
|---|---|
| Terminal Type | Lugs |
| For Use With | Eaton Pow-R-Line Panelboards, Series C Panelboards, Switchboards, Motor Control Centers |
| Wire Gauge | 14-10 AWG (Cu/Al) |
| Max Wire | 10 AWG |
| Min Wire | 14 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment |
|---|---|
| Accessories | Shunt Trip (240VAC) |
| Standards | CSA C22.2 No. 5, Federal Specification W-C-375B, NEMA AB-1, UL 489 |
| Approval | CSA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Reverse Feed, Non-Interchangeable Trip |
The S2 suffix indicates that this breaker includes a factory-installed 110-240V AC or DC shunt trip. This allows the breaker to be tripped remotely via a control signal.
This G-frame breaker is designed for use in Eaton Pow-R-Line panelboards, legacy Series C panelboards, switchboards, and motor control centers.
The GHB series is strictly a bolt-on breaker. It secures directly to the panelboard bus using screws, providing a secure connection that resists vibration and thermal cycling in commercial and industrial environments.
Yes. While primarily used in 480Y/277V AC systems, this breaker is also rated for 125/250V DC applications with a 14kAIC interrupting capacity, making it suitable for industrial DC control panels and battery systems.
No. This breaker features a fixed thermal-magnetic trip unit. The LI designation means it provides Long-Time (thermal overload) and Instantaneous (magnetic short-circuit) protection, but neither function can be manually adjusted in the field.
The factory-installed shunt trip allows the breaker to be opened remotely via a control voltage signal. This is critical for emergency shutdown systems, allowing operators or automated safety relays to instantly de-energize the circuit during a hazard.
The factory-installed lugs accept 14 AWG to 10 AWG conductors. They are dual-rated for both copper (Cu) and aluminum (Al) wire, providing flexibility during installation.
This breaker belongs to the Eaton Series C G-frame family. It shares the same physical footprint as other GHB, GHC, and GD breakers, making it a direct fit for compatible Pow-R-Line panelboards.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.