| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | GHB3030S1 |
| Series | GHB |
| Amperage | 30A |
| Poles | 3 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480Y/277VAC, 125/250VDC |
| Phase | 3 |
| AIC Rating | 65kA @ 240VAC, 14kA @ 480Y/277VAC, 14kA @ 125/250VDC |
| Terminal Type | Lugs |
|---|---|
| For Use With | Eaton Pow-R-Line Panelboards, Eaton Series C Panelboards, Switchboards, Motor Control Centers |
| Wire Gauge | 10-1/0 AWG (Cu/Al) |
| Max Wire | 1/0 AWG |
| Min Wire | 10 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Auxiliary Switch, Undervoltage Release, Alarm Switch |
|---|---|
| Accessories | Shunt Trip (120VAC) |
| Standards | CSA C22.2 No. 5, Federal Specification W-C-375B, UL 489 |
| Approval | CSA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Reverse Feed, Non-Interchangeable Trip |
The S1 suffix indicates this breaker is equipped with a factory-installed 120VAC shunt trip. This allows the breaker to be tripped remotely via a control signal, making it ideal for emergency stop circuits or automated load shedding.
The factory-installed 120VAC shunt trip includes pigtail leads that exit the rear left side of the breaker case. These leads must be wired to a dedicated control circuit with cutoff provisions.
Yes, this thermal-magnetic circuit breaker is suitable for reverse feed applications. You can safely supply line power to either the top or bottom terminals without affecting the breaker's protection characteristics.
This G-Frame bolt-on breaker is engineered for installation in Eaton Pow-R-Line panelboards, Series C panelboards, motor control centers, and compatible switchboards.
Yes. Eaton acquired the electrical divisions of both Westinghouse and Cutler-Hammer. A GHB3030S1 breaker bearing any of these three brand names is physically and electrically identical and can be used interchangeably.
No, this G-Frame breaker comes with a fixed thermal and fixed magnetic trip unit. The long-time and instantaneous trip parameters are factory set for 30 amps and cannot be adjusted in the field.
This Series C breaker utilizes a patented contact design featuring high-speed blow-open action. When a high-level fault occurs, electromechanical forces rapidly separate the contacts before the mechanical trip mechanism fully actuates, reducing let-through current.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.