ABB / General ElectricFBH36TE045RV
Quantity
New
Quantity
ABB / General ElectricFBH36TE045RV
ABB / General ElectricFBH36TE040RV
ABB / General ElectricFBH36TE035RV
ABB / General ElectricFBH36TE025RV
| Brand | ABB / General Electric |
|---|---|
| Series | FBH |
| Amperage | 90A |
| Poles | 3 |
| Mounting Style | Unit Mount |
| Voltage | 240VAC, 480VAC, 600Y/347VAC |
| Phase | 3 |
| AIC Rating | 200kA @ 240VAC, 100kA @ 480VAC, 35kA @ 600Y/347VAC |
| Frame Type | FB100 |
|---|---|
| Terminal Type | Lugs |
| For Use With | GE A-Series Panelboards (Type AD), GE Record Plus Panelboards |
| Wire Gauge | 4-1/0 AWG |
| Max Wire | 1/0 AWG |
| Min Wire | 4 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Auxiliary Switch, Bell Alarm, Shunt Trip, Undervoltage Release |
|---|---|
| Accessories | Line Connections for AD Panels, Load Lugs |
| Standards | CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489 |
| Approval | CE, CSA, HACR, UL, USCG |
| Temp Rating | 40C |
| Construction Features | Current Limiting, HACR Rated, Naval Rated, Reverse Feed |
This breaker is designed for use in GE A-Series Type AD and GE Record Plus panelboards. The RV suffix indicates it includes load lugs and specialized line connections for these specific panels.
The factory installed load lugs accommodate wire gauges from 4 AWG to 1/0 AWG. Ensure you use properly rated copper or aluminum conductors as required by the National Electrical Code for 90A circuits.
Yes, it features a high interrupting rating of 100kAIC at 480VAC and up to 200kAIC at 240VAC, making it suitable for commercial and industrial systems with substantial available fault current.
No, the FBH36TE090RV features fixed thermal and fixed magnetic trip settings. It provides standard long-time and instantaneous protection without field adjustability.
In the GE Record Plus nomenclature, the RV suffix indicates that the breaker is supplied with load lugs and specialized line connections designed specifically for General Electric A-Series Type AD panels.
Always torque the terminal lugs to the manufacturer specifications printed on the breaker faceplate. Proper torque prevents overheating, arcing, and ensures a secure electrical connection.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.