ABB / General ElectricTHHQB2150
Quantity
New
Quantity
ABB / General ElectricTHHQB2150
ABB / General ElectricTHHQB2145
ABB / General ElectricTHHQB2160
ABB / General ElectricTHHQB2140
| Brand | ABB / General Electric |
|---|---|
| Series | THHQB |
| Amperage | 50A |
| Poles | 2 |
| Mounting Style | Bolt-On |
| Voltage | 120VAC, 120/240VAC |
| Phase | 1 |
| AIC Rating | 22kA @ 120VAC, 22kA @ 120/240VAC |
| Frame Type | THQB |
|---|---|
| Terminal Type | Box Lugs |
| For Use With | GE A-Series Panelboards, ReliaGear Panelboards |
| Wire Gauge | 8-3 AWG (Cu), 8-3 AWG (Al) |
| Max Wire | 3 AWG |
| Min Wire | 8 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed |
| Available Options | Shunt Trip, Auxiliary Switch, Padlock Attachment |
|---|---|
| Accessories | Load Side Lugs Included |
| Standards | CSA C22.2 No. 5, UL 489 |
| Approval | CSA, HACR, UL |
| Temp Rating | 10C to 50C |
| Construction Features | HACR Rated, Reverse Feed, Quick-Make/Quick-Break, Internal Common Trip, Visual Trip Indicator, Non-Interchangeable Trip |
This bolt-on breaker is designed for use in GE A-Series panelboards and ReliaGear lighting panelboards. It will not fit in standard residential Q-Line load centers that require plug-on breakers.
Yes. The THHQB22050 shares the same physical dimensions and bolt-on mounting as the THQB22050, but it offers a higher interrupting rating of 22kAIC compared to the 10kAIC rating of the standard THQB version.
The THHQB22050 is a bolt-on breaker intended for commercial panelboards, while the THQL2150 is a plug-on breaker designed for residential load centers. They are not interchangeable.
Yes, this breaker is HACR rated, making it suitable for use with heating, air conditioning, and refrigeration equipment that requires this specific overcurrent protection rating.
For the THHQB22050, the required lug tightening torque depends on the wire size: 40 in-lb for #8 AWG, 45 in-lb for #6 to #4 AWG, and 50 in-lb for #3 AWG.
No. Because the THHQB22050 is a bolt-on breaker, it inherently requires a tool to be removed from the busbar. This satisfies the NEC 408.36(D) requirement for back-fed breakers without needing an additional hold-down kit.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.