| Brand | ABB / General Electric |
|---|---|
| Series | THQC |
| Amperage | 70A |
| Poles | 1 |
| Mounting Style | DIN Rail |
| Voltage | 120/240VAC |
| Phase | 1 |
| AIC Rating | 10kA @ 120/240VAC |
| Frame Type | THQC |
|---|---|
| Terminal Type | Lugs |
| For Use With | 35mm DIN Rail, OEM Panels, Enclosures |
| Wire Gauge | 6-1/0 AWG (Cu), 4-1/0 AWG (Al) |
| Max Wire | 1/0 AWG |
| Min Wire | 6 AWG (Cu), 4 AWG (Al) |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Padlock Attachment |
|---|---|
| Accessories | Line & Load Lugs |
| Standards | CSA C22.2 No. 5, NEMA AB 1, UL 489 |
| Approval | CSA, HACR, UL |
| Temp Rating | 10C to 50C |
| Construction Features | HACR Rated, Quick-Make/Quick-Break, Visual Trip Indicator, Reverse Feed, Non-Interchangeable Trip |
The "WL" suffix signifies that the circuit breaker is supplied with factory-installed line and load lugs. If lugs are not required for the application, the base THQC1170 part number is used.
THQC breakers are designed for 35mm DIN rail or base mounting in OEM panels and enclosures. In contrast, THQL models are plug-in breakers for standard load centers, and THQB models are bolt-on breakers for commercial panelboards.
Yes, this thermal-magnetic breaker features reverse feed capability, allowing it to be back-fed in control panels and enclosures where line and load orientations need to be swapped.
The operating handle trips to a center position between the ON and OFF markings, providing a clear visual indicator that the breaker has tripped due to an overload or short circuit.
Yes. Following ABB's acquisition of GE Industrial Solutions, ABB continues to manufacture the Q-Line series. This unit is the exact replacement for legacy GE-branded THQC1170WL breakers, maintaining identical form, fit, and function.
The LI designation refers to the dual-protection thermal-magnetic mechanism. The Long-Time thermal function protects against sustained overloads by tripping on a delay, while the Instantaneous magnetic function clears severe short circuits immediately.
Yes, this breaker is HACR rated, making it approved for use with heating, air conditioning, and refrigeration motor loads that require specialized overcurrent protection.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.