ABB / General ElectricTHQL2120ST1
Quantity
New
Quantity
ABB / General ElectricTHQL2120ST1
ABB / General ElectricTHQL2130ST1
ABB / General ElectricTHQL2140ST1
ABB / General ElectricTHQL2150ST1
| Brand | ABB / General Electric |
|---|---|
| Series | THQL |
| Amperage | 15A |
| Poles | 2 |
| Mounting Style | Plug-On |
| Voltage | 120/240VAC |
| Phase | 1 |
| AIC Rating | 10kA @ 120/240VAC |
| Frame Type | THQL |
|---|---|
| Terminal Type | Box Lugs |
| For Use With | GE A-Series Panelboards |
| Wire Gauge | 14-8 AWG (Cu), 12-8 AWG (Al) |
| Max Wire | 8 AWG |
| Min Wire | 14 AWG (Cu), 12 AWG (Al) |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed |
| Available Options | Auxiliary Switch, Padlock Attachment |
|---|---|
| Accessories | Shunt Trip |
| Standards | CSA C22.2 No. 5, UL 489, HACR |
| Approval | CSA, UL |
| Temp Rating | 10C to 50C |
| Construction Features | HACR Rated, Internal Common Trip, Quick-Make/Quick-Break |
This plug-in breaker is designed for use in GE A-Series panelboards and compatible GE Powermark Gold load centers that accept 1-inch per pole Q-Line breakers.
The ST1 suffix indicates that this breaker includes a factory-installed 120V shunt trip accessory. This allows the breaker to be tripped remotely via an external control signal or emergency shut-off switch.
As a 2-pole breaker in the standard GE Q-Line family, it requires two 1-inch spaces, totaling 2 inches of space in a compatible plug-on load center.
The box lug terminals accommodate 14 to 8 AWG copper wire or 12 to 8 AWG aluminum wire.
The THQL2115ST1 is a plug-in circuit breaker. If your commercial lighting panel requires a bolt-on connection, you will need the equivalent THQB series breaker instead.
The fixed thermal-magnetic trip unit provides Long-Time and Instantaneous (LI) protection. The thermal component responds to prolonged overloads, while the magnetic component trips instantaneously during severe short circuits.
The integrated shunt trip is commonly used for emergency shutdown applications. It allows the breaker to be opened remotely when tied into a fire alarm system, emergency stop button, or other safety control circuits.
ABB acquired GE Industrial Solutions, meaning GE-branded circuit breakers like the THQL series are now manufactured under the ABB umbrella. They remain fully interchangeable with legacy GE Q-Line breakers.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.