Configured for standalone installations, the Eaton EHD3025L is a 3-pole, 25A molded case circuit breaker. It comes factory-equipped with line and load lugs for independent mounting in commercial settings. The F-Frame breaker is part of the proven Series C family and substitutes the FD3025L. It provides dependable long-time and instantaneous thermal-magnetic protection. With a 14kAIC rating at 480VAC, the breaker is HACR and HID rated and supports reverse feed wiring.
What does the "L" suffix in the EHD3025L catalog number indicate?
The "L" suffix means this breaker is configured for unit mounting (feed-thru) and comes factory-equipped with both line and load lugs, making it ideal for standalone enclosures rather than bolt-on panelboard applications.
Can the EHD3025L replace an FD3025L or HFD3025L breaker?
Yes, it shares the exact same physical footprint as other Series C F-Frame breakers. However, you must verify that the 14kAIC rating at 480VAC is sufficient for your system, as the FD and HFD series offer higher interrupting capacities.
Does the EHD3025L support reverse feed wiring?
Yes, standard thermal-magnetic Series C F-Frame breakers do not have line and load directional restrictions, allowing them to be reverse fed if required by your installation.
Is the EHD3025L suitable for HVAC and lighting applications?
Yes, this breaker is both HACR (Heating, Air Conditioning, and Refrigeration) and HID (High-Intensity Discharge) rated, making it fully compliant for protecting HVAC equipment and specialized lighting circuits.
What wire sizes are compatible with the lugs on this breaker?
The factory-installed line and load lugs accept copper or aluminum conductors ranging from 14 AWG to 1/0 AWG.
Which enclosures and panels are compatible with the EHD3025L?
As a Series C F-Frame breaker, it is designed for Eaton switchboards, motor control centers, and Series C panelboards. Because it is a unit-mount model with line and load lugs, it is also widely used in standalone industrial enclosures.
Can this breaker be used in direct current (DC) systems?
Yes, the EHD3025L is rated for 10kAIC at 250VDC, allowing it to provide reliable thermal-magnetic protection in compatible direct current applications.
What type of trip unit is included in the EHD3025L?
It features a non-interchangeable thermal-magnetic trip unit with fixed long-time and fixed instantaneous (LI) trip functions, providing standard overload and short-circuit protection.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 14 reviews.