Eaton / Cutler-HammerQCGFEP1015
Quantity
New
Quantity
Eaton / Cutler-HammerQCGFEP1015
Eaton / Cutler-HammerQCGFEP1030
Eaton / Cutler-HammerQCGFEP2020
Eaton / Cutler-HammerQBGFEP1020
| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | QCGFEP1020 |
| Series | QCGFEP |
| Amperage | 20A |
| Poles | 1 |
| Mounting Style | Panel Mount |
| Voltage | 120VAC |
| Phase | 1 |
| AIC Rating | 10kA @ 120VAC |
| Frame Type | QC |
|---|---|
| Terminal Type | Box Lugs |
| For Use With | Eaton Quicklag Panelboards, Quicklag Enclosures |
| Wire Gauge | 14-4 AWG |
| Max Wire | 4 AWG |
| Min Wire | 14 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LIG |
| Trip Function | Long-Time, Instantaneous, Ground Fault |
| Trip Adjustability | Fixed |
| Special Classification | GFEP |
|---|---|
| Available Options | Padlock Attachment, DIN Rail Adapter |
| Accessories | Line and Load Lugs Included |
| Standards | CSA C22.2 No. 5, UL 1053, UL 489 |
| Approval | CSA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Non-Interchangeable Trip |
This breaker features a 30mA ground fault trip sensitivity. It is designed for Ground Fault Equipment Protection (GFEP) to protect machinery, heat tracing, and snow melting equipment from damage.
This breaker is designed for use in Eaton Quicklag panelboards and Quicklag enclosures that accept cable-in/cable-out mounted breakers.
The QC series utilizes a cable-in/cable-out mounting design. It does not plug on or bolt directly to a busbar. Instead, it is secured via panel mounting and wired directly to the line and load sides.
The breaker includes a pigtail neutral wire that must be connected directly to the neutral bar in your panelboard to power the ground fault sensing circuitry.
No. Because this breaker has a 30mA trip threshold, it does not meet the 5mA Class A GFCI requirement for protecting personnel in areas like bathrooms, kitchens, or outdoor receptacles.
No. While they are all part of the Quicklag family, QC breakers are cable-in/cable-out, QB breakers are bolt-on, and QCH breakers have a higher interrupting capacity. You must use the specific mounting type required by your panel.
LIG stands for Long-Time, Instantaneous, and Ground-Fault. This means the thermal-magnetic trip unit provides standard overload protection (Long-Time), short-circuit protection (Instantaneous), and equipment-level ground fault protection (Ground-Fault).
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.