Description

Engineered for residential and commercial applications, this 40-amp ground-fault interrupter provides 5mA personnel protection. It features a pigtail neutral connection and built-in self-test capabilities to meet NEC requirements. The plug-on design mounts securely into Eaton CH load centers. It serves as an exact replacement for older CHFGF240 and CH240GF models. Visual trip indicators quickly identify fault conditions alongside standard thermal-magnetic overload defense.

Specifications

Key specifications
Brand Eaton / Cutler-Hammer
Series CHFN
Amperage 40A
Poles 2
Mounting Style Plug-On
Voltage 120/240VAC
Phase 1
AIC Rating 10kA @ 120/240VAC
Fit and installation
Terminal Type Box Lugs
For Use With Eaton CH Load Centers
Wire Gauge 14-3 AWG
Max Wire 3 AWG
Min Wire 14 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LIG
Trip Function Long-Time, Instantaneous, Ground Fault
Trip Adjustability Fixed
Standards and features
Special Classification GFCI
Available Options Padlock Attachment
Accessories Pigtail Neutral
Standards UL 489, UL 943, CSA C22.2 No. 5
Approval UL, CSA
Temp Rating 40C
Construction Features HACR Rated, Visual Trip Indicator, Self-Test, Common Trip

Product FAQs

8 answers
What type of electrical panel accepts the CHFN240GF?

This breaker is designed exclusively for Eaton CH series load centers, which use a 3/4-inch spacing format. It will not fit in Eaton BR series panels or panels from other manufacturers.

What level of ground fault protection does this breaker provide?

It provides Class A ground fault protection with a 5 mA trip sensitivity, which is designed for personnel protection against electrical shock hazards.

Does this breaker require a plug-on neutral panel?

No. This model features a pigtail neutral wire that connects directly to the neutral bus bar, making it compatible with standard, non-plug-on neutral Eaton CH load centers.

What is the recommended tightening torque for the box lug terminals?

The manufacturer specifies a tightening torque of 25 lb-in for the load terminals.

Can I use the CHFN240GF to replace an older CH240GF breaker?

Yes. The CHFN240GF is the direct, updated replacement for legacy part numbers CH240GF and CHN240GF. It fits the same physical footprint and offers the same electrical ratings.

How do I read the diagnostic LED on this breaker?

After a trip event, turning the breaker back on will cause the red LED to blink a specific pattern (1 to 6 times) indicating the cause of the trip. This code repeats 30 times to help you troubleshoot the circuit.

What does it mean if the red LED stays solidly illuminated?

According to Eaton, a constantly illuminated red LED without a blinking pattern is a cosmetic issue on certain models and does not indicate a safety concern or a loss of ground fault protection.

How do I recall the last trip code if I missed the LED blinking?

Turn the breaker handle to the OFF position, press and hold the TEST button, turn the handle to the ON position, and then release the TEST button. The LED will blink the last recorded trip code 30 times.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.