Eaton / Cutler-HammerGHB3060S1
Quantity
New
Quantity
Eaton / Cutler-HammerGHB3060S1
Eaton / Cutler-HammerGHB3070S1
Eaton / Cutler-HammerGHB3050S1
Eaton / Cutler-HammerGHB3080S1
| Brand | Eaton / Cutler-Hammer |
|---|---|
| Series | GHB |
| Amperage | 60A |
| Poles | 3 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480Y/277VAC, 125/250VDC |
| Phase | 3 |
| AIC Rating | 65kA @ 240VAC, 14kA @ 480Y/277VAC, 14kA @ 125/250VDC |
| Frame Type | GHB |
|---|---|
| Terminal Type | Lugs |
| For Use With | Eaton Pow-R-Line C Panelboards, Series C Panelboards, Westinghouse PRL2 Panelboards |
| Wire Gauge | 10-1/0 AWG (Cu/Al) |
| Max Wire | 1/0 AWG |
| Min Wire | 10 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment |
|---|---|
| Accessories | Shunt Trip (240VAC) |
| Standards | CSA C22.2 No. 5, Federal Specification W-C-375B, UL 489 |
| Approval | CSA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Reverse Feed |
The "S2" suffix designates that this breaker includes a factory-installed 240VAC shunt trip mechanism. It features a rear exit with a left pigtail, allowing for remote tripping of the circuit breaker in control systems.
Under UL standards, internal accessories for GHB circuit breakers must be factory-installed because the breaker cases are factory sealed. The GHB3060S2 comes with the 240VAC shunt trip already installed to maintain its UL listing.
No, the 480Y/277VAC slash rating indicates this breaker is only suitable for solidly grounded wye systems where the line-to-ground voltage does not exceed 277V. It cannot be applied on ungrounded or corner-grounded 480V Delta systems.
Yes, the GHB3060S2 is backward compatible with legacy Westinghouse PRL2 panelboards, in addition to modern Eaton Pow-R-Line C and Series C panelboards.
No, this breaker features a non-interchangeable, fixed thermal and fixed magnetic trip unit. It provides standard long-time and instantaneous (LI) protection without field adjustability.
Yes, Eaton G-frame circuit breakers, including the GHB3060S2, are suitable for reverse feed applications.
No, standard load side lugs are included with the breaker. They accept #10 to 1/0 AWG copper or aluminum conductors.
Yes, this breaker is HACR rated, making it suitable for use with heating, air conditioning, and refrigeration equipment branch circuits.
The GHB3060S2 is a bolt-on circuit breaker. It fastens directly to the panelboard bus using mounting screws, providing a secure, vibration-resistant connection for industrial and commercial distribution systems.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.