ABB / General ElectricTHQB2120GFT
Quantity
New
Quantity
ABB / General ElectricTHQB2120GFT
ABB / General ElectricTHQB2120GF
ABB / General ElectricTHQB2130GFT
ABB / General ElectricTHQB2130GF
| Brand | ABB / General Electric |
|---|---|
| Series | THQB |
| Amperage | 15A |
| Poles | 2 |
| Mounting Style | Bolt-On |
| Voltage | 120/240VAC |
| Phase | 1 |
| AIC Rating | 10kA @ 120/240VAC |
| Frame Type | THQB |
|---|---|
| Terminal Type | Box Lugs |
| For Use With | GE A-Series Panelboards, GE AQ Lighting Panels, ReliaGear RQ Panelboards |
| Wire Gauge | 14-8 AWG (Cu), 12-8 AWG (Al) |
| Max Wire | 8 AWG |
| Min Wire | 14 AWG (Cu), 12 AWG (Al) |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LIG |
| Trip Function | Long-Time, Instantaneous, Ground Fault |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Special Classification | GFCI |
|---|---|
| Available Options | Auxiliary Switch, Shunt Trip, Undervoltage Release, Padlock Attachment, Alarm Switch |
| Accessories | Self-Test Feature |
| Standards | CSA C22.2 No. 5, HACR, UL 489, UL 943 |
| Approval | CSA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Common Trip, Quick-Make/Quick-Break, Non-Interchangeable Trip, Self-Test |
This bolt-on breaker is designed for use in GE A-Series panelboards, GE AQ lighting panels, and ABB ReliaGear RQ panelboards. It is not compatible with standard residential plug-on load centers.
No. The THQB2115GFT is a bolt-on breaker intended for commercial panelboards. Standard GE residential load centers typically require Q-Line plug-on breakers, such as the THQL series.
It provides Class A ground fault protection, which trips when it detects a ground fault current of 5mA. This level of protection is designed to protect personnel from electrical shock.
Yes. The T in the THQB2115GFT catalog number indicates that it is a self-testing GFCI breaker. It automatically conducts periodic internal tests to verify that the ground fault protection mechanism remains fully functional.
This breaker features a pigtail neutral wire that must be connected directly to the panel neutral bus bar to power the internal GFCI circuitry. The load neutral wire connects directly to the breaker neutral lug.
No. GFCI breakers require a dedicated neutral for the circuit they protect. Using this breaker on a shared neutral, or multi-wire branch circuit, will cause immediate nuisance tripping.
Yes. The THQB2115GFT is the modern, self-testing replacement for the older, obsolete THQB2115GF and THQB2115GFI models. It fits the same panelboards and provides the same 15A, 2-pole Class A ground fault protection.
The breaker features a center-trip handle position. When a fault or overload occurs, the handle moves to the middle position, making it easy to identify the tripped breaker in a crowded panelboard.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.