| Brand | ABB / General Electric |
|---|---|
| Series | THQB |
| Amperage | 20A |
| Poles | 2 |
| Mounting Style | Bolt-On |
| Voltage | 120/240VAC |
| Phase | 1 |
| AIC Rating | 10kA @ 120/240VAC |
| Frame Type | THQB |
|---|---|
| Terminal Type | Box Lugs |
| For Use With | GE A-Series Panelboards |
| Wire Gauge | 14-8 AWG (Cu), 12-8 AWG (Al) |
| Max Wire | 8 AWG |
| Min Wire | 14 AWG (Cu), 12 AWG (Al) |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LIG |
| Trip Function | Long-Time, Instantaneous, Ground Fault |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Special Classification | GFCI |
|---|---|
| Available Options | Padlock Attachment, Handle Lock |
| Accessories | Self-Test Feature (Integrated) |
| Standards | CSA C22.2 No. 5, UL 489, UL 943, NEMA AB 1 |
| Approval | CSA, HACR, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Common Trip, Quick-Make/Quick-Break, Self-Test |
This bolt-on circuit breaker is designed exclusively for installation in GE A-Series panelboards and AQ lighting panels. It cannot be used in residential load centers and is not interchangeable with plug-in THQL or THQP style breakers.
It provides Class A ground fault protection with a 5mA trip threshold. This is specifically designed for personnel protection to prevent severe electric shock in commercial kitchens, bathrooms, and damp outdoor environments.
The THQB2120GFT features a standard pigtail neutral wire. During installation, this curled white wire must be connected directly to the neutral bus bar in the panelboard to power the internal ground fault sensing circuitry.
The THQB2120GFT2 is the direct manufacturer successor to the THQB2120GFT. It retains the exact same bolt-on mounting, trip ratings, and physical footprint, but adds updated electronics that include an automatic self-test function and LED trip indication.
No. While both models provide identical GFCI protection, the THQL version features a plug-in connection designed for standard residential load centers. The THQB2120GFT utilizes a bolt-on connection required for commercial A-Series panels.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.