| Brand | ABB / General Electric |
|---|---|
| Part Number | THQC2180WL |
| Series | THQC |
| Amperage | 80A |
| Poles | 2 |
| Mounting Style | DIN Rail |
| Voltage | 120/240VAC |
| Phase | 1 |
| AIC Rating | 10kA @ 120/240VAC |
| Frame Type | THQC |
|---|---|
| Terminal Type | Lugs |
| For Use With | DIN Rail Systems, OEM Panels, Enclosures |
| Wire Gauge | 6-1/0 AWG (Cu), 4-1/0 AWG (Al) |
| Max Wire | 1/0 AWG |
| Min Wire | 6 AWG (Cu), 4 AWG (Al) |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed |
| Available Options | Shunt Trip, Auxiliary Switch, Padlock Attachment |
|---|---|
| Accessories | Line and Load Lugs |
| Standards | CSA C22.2 No. 5, UL 489 |
| Approval | CSA, HACR, UL |
| Temp Rating | 10C to 50C |
| Construction Features | HACR Rated, Common Trip, Quick-Make/Quick-Break, Trip-Free Mechanism, Non-Interchangeable Trip |
ABB acquired GE Industrial Solutions. Depending on the production date, the THQC2180WL may feature GE, ABB, or co-branded labeling. The physical dimensions, mounting, and UL listings remain identical across these brands.
The WL suffix specifies that the breaker is factory-equipped with both line and load lugs for feed-thru wiring.
THQC breakers are lug-in, lug-out devices designed for 35mm DIN rail or base mounting in control panels. THQB models are bolt-on for commercial panelboards, and THQL models are plug-in for residential load centers.
The factory-installed lugs accept 6 AWG to 1/0 AWG copper conductors, or 4 AWG to 1/0 AWG aluminum conductors.
No. This breaker is rated for a maximum of 120/240VAC and cannot be used on 277V or 480V systems.
It utilizes a fixed thermal-magnetic trip unit providing Long-Time and Instantaneous (LI) protection. The trip settings are non-adjustable.
Because it uses a DIN rail mount and feed-thru lug connections, the THQC2180WL is typically installed in OEM machinery panels, industrial control enclosures, and automation systems rather than standard distribution panelboards.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.