| Brand | ABB / General Electric |
|---|---|
| Part Number | TJK636500-R |
| Series | TJK |
| Amperage | 500A |
| Poles | 3 |
| Mounting Style | Unit Mount |
| Voltage | 240VAC, 480VAC, 600VAC, 250VDC, 500VDC |
| Phase | 3 |
| AIC Rating | 42kA @ 240VAC, 30kA @ 480VAC, 22kA @ 600VAC, 20kA @ 250VDC, 20kA @ 500VDC |
| Terminal Type | Lugs |
|---|---|
| For Use With | GE A-Series Panelboards, GE J600 Panelboards, Switchboards, Motor Control Centers |
| Wire Gauge | (2) 4/0 AWG-350 kcmil (Cu) or (2) 300-500 kcmil (Al) |
| Max Wire | 500 kcmil |
| Min Wire | 4/0 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Adjustable Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Lug Kits |
|---|---|
| Accessories | Lugs (TCAL63) |
| Standards | CSA C22.2 No. 5.1, NEMA AB 1, UL 489 |
| Approval | CSA, UL |
| Temp Rating | 40C |
| Construction Features | Interchangeable Trip Unit |
This J-Frame breaker is designed for use in GE A-Series panelboards, GE J600 panelboards, switchboards, and motor control centers. Verify your specific enclosure accepts 600-amp frame unit-mount breakers.
The included lugs accommodate two 4/0 AWG to 350 kcmil copper conductors, or two 300 to 500 kcmil aluminum conductors per phase. Always apply the manufacturer recommended torque during installation.
This breaker features a thermal-magnetic trip unit with fixed thermal (Long-Time) protection and an adjustable magnetic (Instantaneous) trip. The adjustable magnetic dial allows you to tune the short-circuit response to properly coordinate with downstream protective devices.
ABB acquired GE Industrial Solutions in 2018. Legacy GE molded case circuit breakers like the TJK series may arrive with either GE or ABB branding, but they are physically and electrically identical.
It is a unit-mount, bolt-on circuit breaker. It requires bolted connections to the busbar or mounting assembly rather than plugging directly into a bus structure.
Installation must be performed by a licensed electrician. Always de-energize the panelboard, switchboard, or motor control center before servicing, and use appropriate personal protective equipment (PPE) to guard against arc flash and shock hazards.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.