ABB / General ElectricTEL136030WL
Quantity
Re-Certified
Quantity
ABB / General ElectricTEL136030WL
ABB / General ElectricTEL134035WL
ABB / General ElectricTEL136070
ABB / General ElectricTEL136125
| Brand | ABB / General Electric |
|---|---|
| Part Number | TEL136020-R |
| Series | TEL |
| Amperage | 20A |
| Poles | 3 |
| Mounting Style | Unit Mount |
| Voltage | 240VAC, 480VAC, 600VAC, 250VDC, 500VDC |
| Phase | 3 |
| AIC Rating | 100kA @ 240VAC, 65kA @ 480VAC, 25kA @ 600VAC, 10kA @ 250VDC, 10kA @ 500VDC |
| Terminal Type | Lugs |
|---|---|
| For Use With | GE A-Series Panelboards, Switchboards, Motor Control Centers |
| Wire Gauge | 14-4 AWG (Cu/Al) |
| Max Wire | 4 AWG |
| Min Wire | 14 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Bell Alarm |
|---|---|
| Accessories | Load Side Lugs Included |
| Standards | CSA C22.2 No. 5, NEMA AB 1, UL 489 |
| Approval | CSA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, High Interrupting Capacity, Common Trip, Trip-Free Mechanism, Quick-Make/Quick-Break, Non-Interchangeable Trip, Reverse Feed |
This unit-mount E-frame breaker is designed for installation in GE A-Series panelboards, switchboards, and motor control centers.
Yes, this breaker is rated for DC systems. It provides up to 10kA interrupting capacity at both 250VDC and 500VDC.
Following ABB acquiring GE Industrial Solutions, legacy GE E-frame breakers like the TEL series are often replaced by the ABB Tmax XT2N series for facility upgrades. Exact replacements depend on the specific panelboard and mounting hardware.
Torque values depend on the wire size used in the 14-4 AWG lugs. Typically, 14 to 10 AWG conductors require 35 in-lb, while 8 to 4 AWG conductors require 100 in-lb. Always confirm with the manufacturer label on the breaker before terminating.
In GE E-frame nomenclature, the L designates a high interrupting capacity tier. The TEL136020 delivers 65kAIC at 480VAC and 100kAIC at 240VAC, offering greater fault current protection than standard TED or THED models.
No, this is a bolt-on, unit-mount molded case circuit breaker. It requires direct bolting to the bus or mounting pan in compatible GE enclosures and does not snap onto a DIN rail.
No, this is a standard thermal-magnetic breaker equipped with fixed long-time and instantaneous (LI) trip functions. It does not provide GFCI or AFCI protection.
No, this breaker features fixed thermal and fixed magnetic trip elements. The long-time and instantaneous trip functions cannot be adjusted in the field.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.