| Brand | ABB / General Electric |
|---|---|
| Series | THQB |
| Amperage | 15A |
| Poles | 2 |
| Mounting Style | Bolt-On |
| Voltage | 120/240VAC |
| Phase | 1 |
| AIC Rating | 10kA @ 120/240VAC |
| Frame Type | THQB |
|---|---|
| Terminal Type | Box Lugs |
| For Use With | GE A-Series Panelboards |
| Wire Gauge | 14-8 AWG (Cu), 12-8 AWG (Al) |
| Max Wire | 8 AWG |
| Min Wire | 14 AWG (Cu), 12 AWG (Al) |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed |
| Available Options | Auxiliary Switch, Padlock Attachment |
|---|---|
| Accessories | Shunt Trip (120VAC) |
| Standards | CSA C22.2 No. 5, HACR, UL 489 |
| Approval | CSA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Non-Interchangeable Trip, Quick-Make/Quick-Break, Common Trip |
The ST1 suffix indicates that this breaker includes a factory-installed 120VAC shunt trip mechanism. This allows the breaker to be tripped remotely via an external control signal, which is commonly used for emergency shutdowns or automated safety systems.
Although it is a 2-pole breaker, the factory-installed shunt trip requires an additional pole space. Therefore, the THQB2115ST1 requires three standard 1-inch panel spaces in your GE A-Series panelboard or AQ lighting panel.
The factory-installed shunt trip on the THQB2115ST1 requires a 120VAC control signal to operate and remotely open the breaker contacts.
No. The THQB2115ST1 is a bolt-on breaker designed specifically for commercial panelboards, such as the GE A-Series. It will not fit in standard residential GE PowerMark load centers, which require plug-in style THQL breakers.
No, the shunt trip mechanism on the THQB2115ST1 is factory-installed and cannot be added in the field. If your application requires remote tripping capabilities, you must purchase a breaker with the ST1 suffix already integrated.
The THQB2115ST1 has a standard interrupting rating of 10kAIC at 120/240VAC. The THHQB version is the high-interrupting model, which raises the short-circuit rating to 22kAIC. Both versions feature the same bolt-on mounting and 120VAC shunt trip.
ABB acquired GE Industrial Solutions in 2018. Depending on the manufacturing date, the THQB2115ST1 may be branded as either ABB or General Electric. The form, fit, function, and catalog numbers remain identical regardless of the label.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.