Providing robust electrical protection, the Square D QDM32225TN is a 225A, three-pole molded case circuit breaker. It belongs to the PowerPacT Q-Frame series, offering fixed long-time and instantaneous trip functions. The bolt-on configuration allows for secure mounting into Square D panelboards, switchboards, and EZ Meter-Pak centers. It replaces discontinued Q23225 breakers. With a 25 kAIC rating at 240VAC, the unit includes a Visi-Trip visual indicator and load-side terminal nuts.
This Q-Frame breaker is designed for installation in Square D EZ Meter-Pak Meter Centers, as well as compatible unit-mount panelboards and switchboards.
What wire sizes are accepted by the terminals on this breaker?
The lugs accommodate aluminum or copper conductors ranging from 4 AWG to 300 kcmil.
What does the LI trip function code indicate?
LI stands for Long-Time and Instantaneous. The long-time function provides thermal protection against sustained overloads, while the instantaneous magnetic function trips the breaker immediately during a short circuit.
Can the trip thresholds be adjusted on the QDM32225TN?
No, this breaker features a fixed thermal-magnetic trip unit. The long-time and instantaneous trip settings are factory-calibrated and cannot be modified in the field.
What does the TN suffix mean in the QDM32225TN catalog number?
The TN suffix designates the terminal configuration. It indicates that the breaker is equipped with mounting studs on the OFF end (without nuts or washers) for bus connections, rather than standard cable lugs on both ends.
What is the difference between Square D QDM and QDA circuit breakers?
QDM breakers are unit-mount devices designed to bolt onto busbars in meter centers, standard panelboards, or switchboards. QDA breakers feature a specialized plug-on jaw configuration exclusively for use in Square D I-Line panelboards.
Can I use this breaker in an I-Line panelboard?
No, the QDM32225TN is a bolt-on, unit-mount breaker. I-Line panelboards require breakers with an I-Line plug-on jaw configuration, such as the QDA series.
Does this breaker include integrated ground fault protection?
No, the QDM32225TN provides standard thermal-magnetic overcurrent and short-circuit protection. It does not feature built-in equipment ground fault protection (LSIG) or personnel ground fault circuit interruption (GFCI).
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.