General Electric TMQV22225MM 2 Pole Circuit Breaker

ABB / General Electric TMQV22225MM - 225A 2 Pole Molded Case Circuit Breaker

New

$754.00 In Stock

Quantity

Similar Items

Description

A drop-in replacement for legacy TMQD22225 units, the GE TMQV22225MM provides maximum amperage capacity for modular metering centers. This 2-pole, 225A breaker utilizes fixed thermal and magnetic trip elements to ensure precise LI protection. Designed exclusively for GE Meter Mod III meter stacks, the breaker features a rugged bolt-on mounting style. Boasting a 100kAIC rating at 240VAC, this HACR-rated main breaker offers superior fault mitigation and includes the required mounting kit.

Specifications

Key specifications
Brand ABB / General Electric
Part Number TMQV22225MM
Series TMQV
Amperage 225A
Poles 2
Mounting Style Bolt-On
Voltage 240VAC
Phase 1
AIC Rating 100kA @ 240VAC
Fit and installation
Frame Type TMQV
Terminal Type Lugs
For Use With GE Meter Mod III Meter Stacks
Wire Gauge #4 AWG - 4/0 AWG (Cu/Al)
Max Wire 4/0 AWG
Min Wire 4 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Fixed Magnetic
Standards and features
Available Options Lug Kits
Accessories Mounting Hardware Kit
Standards UL 489, CSA C22.2 No. 5
Approval UL
Temp Rating 40C
Construction Features HACR Rated, Tenant Main, Non-Interchangeable Trip, Extra High Interrupting Capacity

Product FAQs

6 answers
What is the direct replacement for the obsolete GE TMQD22225 breaker?

The TMQV22225MM is the direct, drop-in replacement for the legacy TMQD22225 tenant main breaker. It maintains the same physical footprint and upgrades the interrupting capacity to 100kAIC.

What equipment is the TMQV22225MM designed to be installed in?

This breaker is specifically designed as a tenant main breaker for GE Meter Mod III modular metering stacks. It fits 200A and 225A two-pole meter sockets.

What does the MM suffix in the TMQV22225MM catalog number indicate?

The MM suffix indicates that the breaker includes the necessary factory mounting kit required for secure bolt-on installation into GE Meter Mod III meter stacks.

What does the 100kAIC rating signify for this tenant main breaker?

The 100kAIC rating means the breaker can safely interrupt up to 100,000 amps of fault current at 240V. This extra-high interrupting capacity makes it suitable for commercial and multi-family metering applications with high available fault currents.

Can I use the TMQV22225MM in a standard GE PowerMark Gold load center?

No, the TMQV frame is a specialized tenant main breaker built exclusively for GE Meter Mod III meter stacks. It is not compatible with standard residential load centers.

Are the load lugs included with the TMQV22225MM breaker?

Yes, this breaker comes with factory-installed load-side lugs that accept 4 AWG to 4/0 AWG copper or aluminum conductors.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.